1 Electrical network protection Sepam IEC For Sepam series 20/40/60/80 User s manual 0/203
2 Safety instructions 0 Safety symbols and messages Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. ANSI symbol. IEC symbol. Risk of electric shock The addition of either symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed. Safety alert This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death. Safety messages DANGER DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury. CAUTION CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury. NOTICE NOTICE is used to address practices not related to physical injury. Important notes Restricted liability Electrical equipment should be serviced and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this manual. This document is not intended as an instruction manual for untrained persons. Device operation The user is responsible for checking that the rated characteristics of the device are suitable for its application. The user is responsible for reading and following the device s operating and installation instructions before attempting to commission or maintain it. Failure to follow these instructions can affect device operation and constitute a hazard for people and property. Protective grounding The user is responsible for compliance with all the existing international and national electrical codes concerning protective grounding of any device. SEPED305002EN - 0/203
3 IEC Contents Presentation 2 IEC protocol 3 Access to Sepam data 5 Sepam profile 6 Sepam data table 0 Sepam data table - Monitoring direction Sepam data table - Control direction 20 Configuring the interfaces 2 Commissioning and diagnosis 25 Appendix : Sepam data coding 28 Appendix 2: File transfer 32 General 32 ASDU coding 36 Frame sequences exchanged in order to read a file 39 Use of files by the supervisor 4 SEPED305002FR - 0/203
4 IEC Presentation 0 PB03454 General IEC enables Sepam units to be connected to a supervisor or other device featuring an IEC channel. Communication is based on the master/slave principle: b Sepam is always a slave station. b The master is the supervisor or another device. IEC is available via the ACE969-2 interface. ACE969TP-2 interface. ACE969-2 is a multiprotocol interface with two independent ports: b The S-LAN (Supervisory-Local Area Network) port is used to connect Sepam to a network dedicated to supervision. b The E-LAN (Engineering-Local Area Network) port is reserved for specific Sepam setup, operating and adjustment functions. This port is connected to the SFT284 software tool. PB03453 The ACE969-2 interface is available in two versions, linked to the physical interface of the S-LAN supervision port: b ACE969TP-2 (Twisted Pair) for an S-LAN network, 2-wire RS 485 serial link b ACE969FO-2 (Fiber Optic) for a fiber-optic star or ring S-LAN The E-LAN engineering port is always a 2-wire RS 485 type port. ACE969FO-2 interface. Accessible data DE805 S-LAN SFT284 Sepam series 20 E-LAN ACE969-2 IEC via the S-LAN port provides access to a great deal of information, in particular: b Reading of metering information b Reading of status conditions and time-tagged events b Transfer of files including disturbance records and for Sepam series 60 and Sepam series 80, tripping contexts out-of-sync context, Motor Start records, Motor Trend records and Data Log records, b Time-setting and synchronization b Transmission of remote controls The actual list depends on the application, the type of Sepam, the enabled functions, and the ACE969-2 interface parameter settings. Sepam series 40 ACE969-2 Sepam series 60/80 Connecting the SFT284 tool to the E-LAN port also provides access to all Sepam function parameters and operating data: b Hardware configuration parameters b Remote settings for protection functions b Switching on/off of protection functions b Retrieval of disturbance records and, for Sepam series 60 and Sepam series 80, Motor Start records, Motor Trend records and Data Log records b Display of metering and diagnosis information b Display of logic states b Display of alarms ACE969-2 Two independent networks: S-LAN: IEC supervision E-LAN: For SFT284 operating functions. 2 SEPED305002EN - 0/203
5 IEC IEC protocol 0 Selected application functions of IEC Selected application service data units of IEC Selected application information elements of IEC Selected link transmission procedures of IEC Selected transmission frame formats of IEC Fiber-optic system based on IEC or IEC and IEC and IEC or copper-wirebased system according to EIA RS-485 IEC profile. User process Application layer (Layer 7) Link layer (Layer 2) Physical layer (Layer ) Presentation The IEC protocol is a companion standard for the informative interface of protection equipment. Standard IEC was prepared by IEC technical committee 57 (Power system control and associated s). It is a companion standard for the basic standards in series IEC As a companion standard, it adds semantics to the definitions and functional profiles specified in the basic standards: b Definition of the particular uses for information objects b Definition of specialist information objects b Definition of service procedures or additional parameters in respect of the basic standards Standard IEC defines between protection equipment and devices of a control system (supervisor or RTU) in a substation. Standard IEC can be obtained in full from the International Electrotechnical Commission: SEPED305002EN - 0/203 3
6 IEC IEC protocol 0 Protocol principle General Standard IEC defines a multipoint protocol via which information can be exchanged between a control system (supervisor or RTU) and one or more protection devices. The control system is the master and the protection devices are the slaves. Each slave is identified by a unique address between and 254. Address 255 is reserved for broadcast frames. Standard IEC defines two different methods for exchanging information: b The first is based on the use of predefined data structures (ASDU - Application Service Data Units) and application procedures supporting the transmission of standardized information. b The other uses generic services supporting the transmission of any type of information. Sepam does not use generic services. The protocol distinguishes between: b The Monitoring direction for the transmission of ASDUs sent by a protection device (slave device) to the control system (master device). b The Control direction for ASDUs sent by the control system to a protection device. Monitoring direction Communication is based on the cyclic transmission of link-layer polling requests by the master in order to invite the slave to send its data. b Class data polling is usually used for event transmission. b Class 2 data polling is used for the cyclic transmission of metering information. Control direction The master can send: b General commands (enable/disable functions: protection, recloser, etc.) b A general interrogation request to obtain the current value of slave equipment status conditions and indications b A transmission request for disturbance records and other records b Time synchronization commands b Commands to reset the interface Communication initialization The slave interface only becomes operational once an initialization request sent by the master device has been received. The absence of polling by the master is detected by the slave and this stops. To re-establish, the master device must send a reset request. Information characteristics All information exchanged between the control system and the protection equipment features: b A function number b An information number b The ASDU number used to transmit the information b The cause of the transmission 4 SEPED305002EN - 0/203
7 IEC IEC protocol 0 Access to Sepam data Sepam is a multifunctional digital relay, which supplies a great deal of information. Sepam data is categorized on the basis of function. Compliant with the data model defined in IEC , all data is identified by a function number (FUN) and an information number (INF). A detailed description of the Sepam data table, including function number and information number, appears in the Sepam data table section. List of IEC standard functions Sepam supports the subset of standard functions shown below. Sepam uses the standard FUN and INF numbers for these functions. FUN Function name 255 System 60 Overcurrent protection List of Sepam-specific functions Sepam uses private FUN and INF numbers for these functions. FUN Function name States and indications 20 Sepam supervision 2 Switchgear and network 22 Logic equations 3 Logic inputs (MES no. ) 32 Logic inputs (MES no. 2) 33 Logic inputs (MES no. 3) 4 Logipam group 42 Logipam group 2 43 Logipam group 3 Protections 00 Overcurrent protections 0 Directional current protections 02 Voltage protections 03 Frequency protections 04 Motor/generator protections 05 Miscellaneous protections 06 Thermal protections 07 Power protections 08 Differential protections 09 Speed protection Measurements 0 Temperature measurements Additional measurements 2 Additional measurements 2 List of standard ASDUs Sepam supports the subset of standard ASDUs shown below. ASDU Function Monitor direction Time-tagged message b 2 Time-tagged message with relative time b 5 Identification message b 6 Time synchronization b b 7 General interrogation b 8 End of general interrogation b 9 Measurands II b 20 General command b Control direction List of private ASDUs In addition to the functions and standard ASDU, Sepam supports a File transfer function, which uses private ASDUs. This function can be used to retrieve: b Disturbance records b For Sepam series 60 and Sepam series 80 only: v Tripping contexts v Out-of-sync context v Motor Start records v Motor Trend records v Data Log records. Disturbance, Motor Start, Motor Trend and Data Log records are supplied in COMTRADE format. ASDU Function Monitoring direction 254 Transfer command b 255 Transfer response b Control direction SEPED305002EN - 0/203 5
8 IEC IEC protocol 0 Sepam profile The Sepam profile defines how the options of standard IEC are implemented by Sepam. The presentation format and numbering used in this section are intentionally based on clause "8. Interoperability" of standard IEC Indicates that Sepam supports the option from the standard. Indicates that Sepam does not support the option. 8. Interoperability 8. Physical layer 8.. Electrical interface EIA RS-485. Number of loads... for one protection device. Nota : EIA RS-485 standard defines unit loads so that 32 of them can be operated on one line. For detailed information refer to clause 3 of EIA RS-485 standard Optical interface Glass fiber. Plastic fiber. F-SMA type connector. BFOC/2.5 type connector Transmission speed 9,600 bps. 9,200 bps. 8.2 Link layer There are no choices for the link layer. 8.3 Application layer 8.3. Transmission mode for application data Mode (least significant byte first), as defined in 4.0 of IEC , is used exclusively in this companion standard COMMON ADDRESS OF ASDU One COMMON ADDRESS OF ASDU (identical to station address) More than one COMMON ADDRESS OF ASDU Selection of standard information numbers in monitoring direction System functions in monitoring direction INF <0> <0> <2> <3> <4> <5> Semantics End of general interrogation Time synchronization Reset FCB Reset CU Start/restart Power on 6 SEPED305002EN - 0/203
9 IEC IEC protocol 0 Sepam profile Status indications in monitoring direction INF Semantics <6> Auto-recloser active <7> Teleprotection active <8> Protection active <9> LED reset <20> Monitoring direction blocked <2> Test mode <22> Local parameter setting <23> Characteristic <24> Characteristic 2 <25> Characteristic 3 <26> Characteristic 4 <27> Auxiliary input <28> Auxiliary input 2 <29> Auxiliary input 3 <30> Auxiliary input Supervision indications in monitoring direction INF <32> <33> <35> <36> <37> <38> <39> <46> <47> Semantics Measurand supervision I Measurand supervision V Phase sequence supervision Trip circuit supervision I>> back-up operation VT fuse failure Teleprotection disturbed Group warning Group alarm Earth fault indications in monitoring direction INF <48> <49> <50> <5> <52> Semantics Earth fault L Earth fault L2 Earth fault L3 Earth fault forward, i.e. line Earth fault reverse, i.e. busbar SEPED305002EN - 0/203 7
10 IEC IEC protocol 0 Sepam profile Fault indications in monitoring direction INF Semantics <64> Start/pick-up L <65> Start/pick-up L2 <66> Start/pick-up L3 <67> Start/pick-up N <68> General trip <69> Trip L <70> Trip L2 <7> Trip L3 <72> Trip I>> (back-up operation) <73> Fault location X in ohms <74> Fault forward/line <75> Fault reverse/busbar <76> Teleprotection signal transmitted <77> Teleprotection signal received <78> Zone <79> Zone 2 <80> Zone 3 <8> Zone 4 <82> Zone 5 <83> Zone 6 <84> General start/pick-up <85> Breaker failure <86> Trip measuring system L <87> Trip measuring system L2 <88> Trip measuring system L3 <89> Trip measuring system E <90> Trip I> <9> Trip I>> <92> Trip IN> <93> Trip IN>> Auto-reclosure indications in monitoring direction INF Semantics <28> CB 'on' by AR <29> CB 'on' by delayed AR <30> AR blocked Measurands in monitoring direction INF Semantics <44> Measurand <45> Measurands I, V <46> Measurands I, V, P, Q <47> Measurands IN, VEN <48> Measurands IL, 2, 3, VL, 2, 3, P, Q, f Generic functions in monitoring direction INF Semantics <240> Read headings of all defined groups <24> Read values or attributes of all entries of one group <243> Read directory of a single entry <244> Read value or attribute of a single entry <245> End of general interrogation of generic data <249> Write entry with confirmation <250> Write entry with execution <25> Write entry aborted 8 SEPED305002EN - 0/203
11 IEC IEC protocol 0 Sepam profile Selection of standard information numbers in control direction System functions in control direction INF <0> <0> Semantics Initiation of general interrogation Time synchronization General commands in control direction INF Semantics <6> Auto-recloser on/off <7> Teleprotection on/off <8> Protection on/off <9> LED reset <23> Activate characteristic <24> Activate characteristic 2 <25> Activate characteristic 3 <26> Activate characteristic Generic functions in control direction INF Semantics <240> Read headings of all defined groups <24> Read values or attributes of all entries of one group <243> Read directory of a single entry <244> Read value or attribute of a single entry <245> General interrogation of generic data <248> Write entry <249> Write entry with confirmation <250> Write entry with execution <25> Write entry aborted Basic application functions Test mode Blocking of monitoring direction Disturbance data Generic services Private data Miscellaneous Measurands are transmitted with ASDU 3 as well as with ASDU 9. As defined in , the maximum MVAL can either be.2 or 2.4 times the rated value. No different rating shall be used in ASDU 3 and ASDU 9, i.e. for each measurand there is only one choice. Measurand Max. MVAL = rated value times.2 or 2.4 Current L Current L2 Current L3 Voltage L-E Voltage L2-E Voltage L3-E Active power P Reactive power Q Frequency f Voltage L - L2 SEPED305002EN - 0/203 9
12 IEC IEC protocol 0 Sepam data table All Sepam data that can be exchanged with a supervisor via the IEC protocol is listed in two tables: b The monitoring direction data table, which lists all Sepam data to be transmitted to the supervisor. b The control direction data table, which lists all supervisor data to be transmitted to Sepam. Description of the Sepam data table The following information is provided for each data item: b The ASDU (Application Service Data Unit) number b The value of the FUN (Function) and INF (Information) identifiers b The value of the COT (Cause Of Transmission) field b A GI (General Interrogation) marker b The Sepam data semantic b The Sepam series for which the data is available For Sepam series 20, Sepam B2X (dedicated to voltage applications) are distinct from Sepam S20, T20 and M20 (dedicated to current applications). The effective availability of a Sepam data item also depends on the Sepam type and function parameter settings. ASDU: Application Service Data Unit The ASDU number identifies the standard data structure used by Sepam for data transmission. FUN and INF: Function number and information number Each Sepam data item is identified by: b The number of the function to which the data belongs: FUN b The information number of the basic data: INF COT: Cause Of Transmission The COT value shows the cause of transmission of the data. Monitoring direction In the monitoring direction, Sepam uses the following COT values: COT Label Spontaneous Information produced spontaneously following a change of state (date-tagged event) 2 Cyclic Information produced cyclically by Sepam (measurements) 3 Reset (FCB) Response to command to reset the frame count bit (FCB) 4 Reset (CU) Response to command to reset the unit (CU) 5 Start/restart Response to command to initialize the interface 8 Time synchronization Acknowledgment of time synchronization command 9 General interrogation Information produced in response to a general interrogation command 0 End of general interrogation Termination message of a general interrogation cycle 2 Remote operation Change of state resulting from a supervisor command 20 Positive acknowledgement Positive acknowledgment of command 2 Negative acknowledgement Negative acknowledgment of command Control direction In the control direction, Sepam supports the following COT values: COT Label 8 Time synchronization Time synchronization command 9 General interrogation Initialization of a general interrogation cycle 20 General command Command from the supervisor such as open/close breaker, enable/disable a function, etc. GI: General Interrogation The GI marker indicates whether the data is produced in response to a general interrogation request. For this data, each change of state ("OFF" to "ON" and "ON" to "OFF") is also transmitted spontaneously. 0 SEPED305002EN - 0/203
13 IEC IEC protocol 0 Sepam data table - Monitoring direction ASDU FUN INF COT GI IEC semantic Sepam series 20 Sepam B2X Other series 40 Sepam series System functions End of general interrogation b b b b b Time synchronization b b b b b Reset frame count bit (FCB) b b b b b Reset unit (CU) b b b b b Start/restart b b b b b Sepam series 80 ASDU FUN INF COT GI IEC semantic Sepam semantic Sepam series 20 Sepam B2X Other series 40 Sepam series Maximum overcurrent protection (IEC standard function) 60 6, 9, 2, 20, 2 b Auto-recloser active Recloser on b b b b 60 9, 2, 20, 2 LED reset , b Monitoring direction blocked 60 23, 9, 2, 20, , 9, 2, 20, 2 Sepam reset after fault Monitoring direction blocked b Characteristic Setting group A in service b Characteristic 2 Setting group B in service b b b b b b b b b b b b b b b b b b 60 32, 9 b Measurand supervision I Phase-CT fault b b b 60 33, 9 b Measurand supervision V Phase-VT fault b b b 60 35, 9 b Phase sequence supervision Main-phase reverse rotation b b b 60 36, 9 b Trip circuit supervision Matching fault or b b b b b Trip Circuit Supervision General trip Trip b b b b b Breaker failure Protection 50BF b b b b Trip I> Protection 50/5 unit Trip I>> Protection 50/5 unit Trip IN> Protection 50N/ 5N unit Trip IN>> Protection 50N/ 5N unit CB 'on' by Auto-recloser Recloser: reclosing successful b (unit group A) b b b b (unit 2 b b b group A) b (unit b b b group A) b (unit 2 b b b group A) b b b b Sepam series 80 SEPED305002EN - 0/203
14 IEC IEC protocol 0 Sepam data table - Monitoring direction ASDU FUN INF COT GI Sepam semantic Sepam series 20 Sepam B2X Other series 40 Sepam series Sepam supervision 20, 9 b Sepam partial fault b b b b b 20 2, 9 b Sepam major fault b b b b b 20 3, 9 b MET 48- module sensor fault b b b b 20 4, 9 b MET 48-2 module sensor fault b b b 20 5, 9 b Control fault b b b b b 20 6, 9 b Residual VT fault b b b 20 7, 9 b Additional phase CT fault b 20 8, 9 b Additional phase VT fault b 20 9, 9 b Additional residual VT fault b 20 0 Min. V_aux b b 20 Max. V_aux b b 20 2 Battery low or absent b b 20 3, 9 b Test mode b b 20 4, 9, 2, b S-LAN monitoring active b b b 20, Ethernet fault b b 20 6 New disturbance recording available b b 20 7 Motor Start in progress b b 20 8 Data Log record in progress b b 20 9 New Data Log record available b b Discrepancy in the phase rotation direction selection command b b 2 Switchgear and network 2, 9, 2, b Device closed b b 20, 2 2 2, 9 b Device racked out b b 2 3 SF6 alarm b b b 2 4, 9 b Earthing switch closed b b 2 5 Thermistor alarm b b b 2 6 Thermistor tripping b b b 2 7 Buchholz alarm b b b 2 8 Buchholz tripping b b b 2 9 Thermostat alarm b b b 2 0 Thermostat tripping b b b 2 Pressure alarm b b b 2 2 Pressure tripping b b b 2 3 External tripping b b b 2 4 External tripping 2 b b b 2 5 External tripping 3 b b b 2 6 Load shedding b b 2 7 Restart b b 2 8, 9 b Additional phase reverse rotation b b 2 9, 9 b Recloser ready b b b 2 20 Recloser: final trip b b b b 2 2 Send blocking signal b b b b 2 22 Send blocking signal 2 b b b 2 23, 9 b Closing circuit supervision b b 2 24 Request for synchro-checked closing b b 2 25 Synchronization stop b b 2 26 Synchronization failure b b 2 27 Synchronization successful b b 2 28 du synchronization failure b b 2 29 dphi synchronization failure b b 2 30 df synchronization failure b b 2 3 Manual capacitor step control b 2 32 Automatic capacitor step control b 2 33 Capacitor step matching fault b 2 34 Capacitor step 2 matching fault b 2 35 Capacitor step 3 matching fault b 2 36 Capacitor step 4 matching fault b 2 37 Coupling closing order b b 2 38 Coupling synchronization failure b b 2 39 Tripping by automatic transfer (AT) b 2 40 Cumulative breaking current monitoring b b Sepam series 80 2 SEPED305002EN - 0/203
15 IEC IEC protocol 0 Sepam data table - Monitoring direction ASDU FUN INF COT GI Sepam semantic Sepam series 20 Sepam B2X Other series 40 Sepam series 60 2 Switchgear and network (cont.) , 2 Ack. of command Priority group shutdown b b , 2 Ack. of command Enable/Disable synchro-check b b , 2 Ack. of command Enable/Disable voltage check b b , 2 Ack. of command Close/Open capacitor step b , 2 Ack. of command Close/Open capacitor step 2 b , 2 Ack. of command Close/Open capacitor step 3 b , 2 Ack. of command Close/Open capacitor step 4 b Sepam series 80 SEPED305002EN - 0/203 3
16 IEC IEC protocol 0 Sepam data table - Monitoring direction ASDU FUN INF COT GI Sepam semantic Sepam series 20 Sepam B2X Other series 40 Sepam series Logic equations 22, 9 b V b b b 22 2, 9 b V2 b b b 22 3, 9 b V3 b b b 22 4, 9 b V4 b b b 22 5, 9 b V5 b b b 22 6, 9 b V6 b b b 22 7, 9 b V7 b b b 22 8, 9 b V8 b b b 22 9, 9 b V9 b b b 22 0, 9 b V0 b b b 22, 9 b V b b 22 2, 9 b V2 b b 22 3, 9 b V3 b b 22 4, 9 b V4 b b 22 5, 9 b V5 b b 22 6, 9 b V6 b b 22 7, 9 b V7 b b 22 8, 9 b V8 b b 22 9, 9 b V9 b b 22 20, 9 b V20 b b 22 2, 9 b V_FLAGREC b b b 22 22, 9 b V_TRIPCB b b b 22 23, 9 b V_CLOSECB b b b 22 24, 9 b V_INHIBCLOSE b b b 22 25, 9 b V_RESET b b 22 26, 9 b V_CLEAR b b 22 27, 9 b V_INHIBIT_RESET_LOCAL b b 22 28, 9 b V_SHUTDOWN b b 22 29, 9 b V_DE-EXCITATION b b 22 30, 9 b V_CLOSE_NOCTRL b b 22 3, 9 b V_TRIP_STP b b 22 32, 9 b V_TRIP_STP2 b b 22 33, 9 b V_TRIP_STP3 b b 22 34, 9 b V_TRIP_STP4 b b 22 35, 9 b V_CLOSE_STP b b 22 36, 9 b V_CLOSE_STP2 b b 22 37, 9 b V_CLOSE_STP3 b b 22 38, 9 b V_CLOSE_STP4 b b 22 39, 9 b V_TRANS_ON_FLT b b 22 40, 9 b V_TRANS_STOP b b 22 4, 9 b V_MIMIC_IN_ b b 22 42, 9 b V_MIMIC_IN_2 b b 22 43, 9 b V_MIMIC_IN_3 b b 22 44, 9 b V_MIMIC_IN_4 b b 22 45, 9 b V_MIMIC_IN_5 b b 22 46, 9 b V_MIMIC_IN_6 b b 22 47, 9 b V_MIMIC_IN_7 b b 22 48, 9 b V_MIMIC_IN_8 b b 22 49, 9 b V_MIMIC_IN_9 b b 22 50, 9 b V_MIMIC_IN_0 b b 22 5, 9 b V_MIMIC_IN_ b b 22 52, 9 b V_MIMIC_IN_2 b b 22 53, 9 b V_MIMIC_IN_3 b b 22 54, 9 b V_MIMIC_IN_4 b b 22 55, 9 b V_MIMIC_IN_5 b b 22 56, 9 b V_MIMIC_IN_6 b b 22 57, 9 b V_TRANS_V_EN b b 22 58, 9 b V_MSR_START: MSR activation b b 22 59, 9 b V_DLG_START: DLG activation b b Sepam series 80 4 SEPED305002EN - 0/203
17 IEC IEC protocol 0 Sepam data table - Monitoring direction ASDU FUN INF COT GI Sepam semantic Sepam series 20 Sepam B2X Other series 40 Sepam series 60 3 Logic inputs (MES no. ) 3, 9 b Logic input I I I I0 I0 3 2, 9 b Logic input I2 I2 I2 I02 I02 3 3, 9 b Logic input I3 I3 I3 I03 I03 3 4, 9 b Logic input I4 I4 I4 I04 I04 3 5, 9 b Logic input I2 I2 I2 I05 I05 3 6, 9 b Logic input I22 I22 I22 I06 I06 3 7, 9 b Logic input I23 I23 I23 I07 I07 3 8, 9 b Logic input I24 I24 I24 I08 I08 3 9, 9 b Logic input I25 I25 I25 I09 I09 3 0, 9 b Logic input I26 I26 I26 I0 I0 3, 9 b Logic input I I 3 2, 9 b Logic input I2 I2 3 3, 9 b Logic input I3 I3 3 4, 9 b Logic input I4 I4 32 Logic inputs (MES no. 2) 32 to 4, 9 b Logic inputs I20 to I24 b b 33 Logic inputs (MES no. 3) 3 to 4, 9 b Logic inputs I30 to I34 b 4 Logipam group (Sepam series 80 option) 4 6 to, 9 b TS6 to TS3 b , 2 Ack. of command TC6 b , 2 Ack. of command TC7 b 4 0 to 7 20, 2 Ack. of command TC0 to Ack. of command TC7 42 Logipam group 2 (Sepam series 80 option) to, 9 b TS33 to TS48 b to 29 20, 2 Ack. of command TC2 to Ack. of command TC29 b 43 Logipam group 3 (Sepam series 80 option) to 64, 9 b TS52 to TS64 b to 64 20, 2 Ack. of command TC49 to Ack. of command TC64 Sepam series 80 b b SEPED305002EN - 0/203 5
18 IEC IEC protocol 0 Sepam data table - Monitoring direction ASDU FUN INF COT GI Sepam semantic Sepam series 20 Sepam Sepam Sepam B2X Other series 40 series 60 series Overcurrent protections 2 00 Protection 50/5 unit 3 b (unit b b b group B) Protection 50/5 unit 4 b (unit 2 b b b group B) Protection 50/5 unit 5 b Protection 50/5 unit 6 b Protection 50/5 unit 7 b Protection 50/5 unit 8 b Protection 50N/5N unit 3 b (unit b b b group B) Protection 50N/5N unit 4 b (unit 2 b b b group B) Protection 50N/5N unit 5 b Protection 50N/5N unit 6 b 2 00 Protection 50N/5N unit 7 b Protection 50N/5N unit 8 b Protection 5V unit b b b Protection 5V unit 2 b 0 Directional current protections 2 0 Protection 67 unit b b b Protection 67 unit 2 b b b Protection 67N unit b b b Protection 67N unit 2 b b b 02 Voltage protections 2 02 Protection 27/27S unit b b b b Protection 27/27S unit 2 b b b b Protection 27/27S unit 3 b Protection 27/27S unit 4 b Protection 27D unit b b b b Protection 27D unit 2 b b b b Protection 27R unit b b b b Protection 27R unit 2 b b 2 02 Protection 59 unit b b b b Protection 59 unit 2 b b b b Protection 59 unit 3 b Protection 59 unit 4 b Protection 59N unit b b b b Protection 59N unit 2 b b b b Protection 27S phase b Protection 27S phase 2 b Protection 27S phase 3 b 6 SEPED305002EN - 0/203
19 IEC IEC protocol 0 Sepam data table - Monitoring direction ASDU FUN INF COT GI Sepam semantic Sepam series 20 Sepam B2X Other series 40 Sepam series Frequency protections 2 03 Protection 8H unit b b b b Protection 8H unit 2 b b b 2 03 Protection 8L unit b b b b Protection 8L unit 2 b b b b Protection 8L unit 3 b b b Protection 8L unit 4 b b b Protection 8R unit b b b Protection 8R unit 2 b b 04 Motor/generator protections 2 04 Protection 48/5LR (locked rotor) b b b b Protection 48/5LR (locked rotor at start-up) b b b b Protection 48/5LR (excessive starting time) b b b b 04 4, 9 b Protection 66 b b b b Protection 2B b Protection 50/27 b Protection 64G2/27TN unit b Protection 64G2/27TN unit 2 b Protection 78PS b Protection 24 unit b 2 04 Protection 24 unit 2 b Protection 40 b b 05 Miscellaneous protections 2 05 Protection 46 unit b b b b Protection 46 unit 2 b b b Protection 46BC b 2 05 Protection 47 unit b b b Protection 47 unit 2 b b Protection 37 b b b b Protection 5C unit (capacitor step ) b Protection 5C unit 2 (capacitor step ) b Protection 5C unit 3 (capacitor step 2) b Protection 5C unit 4 (capacitor step 2) b Protection 5C unit 5 (capacitor step 3) b Protection 5C unit 6 (capacitor step 3) b Protection 5C unit 7 (capacitor step 4) b Protection 5C unit 8 (capacitor step 4) b , 2 Ack. of command Reset undercurrent protection b b b Sepam series 80 SEPED305002EN - 0/203 7
20 IEC IEC protocol 0 Sepam data table - Monitoring direction ASDU FUN INF COT GI Sepam semantic Sepam series 20 Sepam B2X Other series 40 Sepam series Thermal protections 06 Protection 49 RMS alarm set point b b b b 06 2 Protection 49 RMS tripping set point b b b b 06 3, 9, 2, b Thermal protection tripping inhibited b b b b 20, 2 06 Protection 38/49T tripping sensor module b b b b 06 2 Protection 38/49T tripping sensor 2 module b b b b 06 3 Protection 38/49T tripping sensor 3 module b b b b 06 4 Protection 38/49T tripping sensor 4 module b b b b 06 5 Protection 38/49T tripping sensor 5 module b b b b 06 6 Protection 38/49T tripping sensor 6 module b b b b 06 7 Protection 38/49T tripping sensor 7 module b b b b 06 8 Protection 38/49T tripping sensor 8 module b b b b 06 2 Protection 38/49T tripping sensor module 2 b b b Protection 38/49T tripping sensor 2 module 2 b b b Protection 38/49T tripping sensor 3 module 2 b b b Protection 38/49T tripping sensor 4 module 2 b b b Protection 38/49T tripping sensor 5 module 2 b b b Protection 38/49T tripping sensor 6 module 2 b b b Protection 38/49T tripping sensor 7 module 2 b b b Protection 38/49T tripping sensor 8 module 2 b b b 06 3 Protection 38/49T alarm sensor module b b b b Protection 38/49T alarm sensor 2 module b b b b Protection 38/49T alarm sensor 3 module b b b b Protection 38/49T alarm sensor 4 module b b b b Protection 38/49T alarm sensor 5 module b b b b Protection 38/49T alarm sensor 6 module b b b b Protection 38/49T alarm sensor 7 module b b b b Protection 38/49T alarm sensor 8 module b b b b 06 4 Protection 38/49T alarm sensor module 2 b b b Protection 38/49T alarm sensor 2 module 2 b b b Protection 38/49T alarm sensor 3 module 2 b b b Protection 38/49T alarm sensor 4 module 2 b b b Protection 38/49T alarm sensor 5 module 2 b b b Protection 38/49T alarm sensor 6 module 2 b b b Protection 38/49T alarm sensor 7 module 2 b b b Protection 38/49T alarm sensor 8 module 2 b b b 07 Power protections 2 07 Protection 32P unit b b b Protection 32P unit 2 b b Protection 32Q b b b 2 07 Protection 37P unit b b Protection 37P unit 2 b b 08 Differential protections 2 08 Protection 64REF unit b b Protection 64REF unit 2 b b Protection 87T2 b 2 08 Protection 87M/87G b 09 Speed protections 09 Protection 2 unit b b 09 2 Protection 2 unit 2 b b 09 3 Protection 4 unit b b 09 4 Protection 4 unit 2 b b Sepam series 80 8 SEPED305002EN - 0/203
21 IEC IEC protocol 0 Sepam data table - Monitoring direction ASDU FUN INF COT GI Sepam semantic Sepam series 20 Sepam B2X Other series 40 Sepam series Standard measurements information elements MEA to MEA9 MEA: Phase current I b b b b MEA2: Phase current I2 b b b b MEA3: Phase current I3 b b b b MEA4: Phase-to-neutral voltage V b b b b MEA5: Phase-to-neutral voltage V2 b b b b MEA6: Phase-to-neutral voltage V3 b b b b MEA7: Active power P b b b MEA8: Reactive power Q b b b MEA9: Frequency f b b b b 0 Temperature measurements information elements: 6 temperatures MEA to MEA6, as a % of full scale (i.e. 200 C) MEA: Temperature sensor module b b b b MEA2: Temperature sensor 2 module b b b b MEA3: Temperature sensor 3 module b b b b MEA4: Temperature sensor 4 module b b b b MEA5: Temperature sensor 5 module b b b b MEA6: Temperature sensor 6 module b b b b MEA7: Temperature sensor 7 module b b b b MEA8: Temperature sensor 8 module b b b b MEA9: Temperature sensor module 2 b b b MEA0: Temperature sensor 2 module 2 b b b MEA: Temperature sensor 3 module 2 b b b MEA2: Temperature sensor 4 module 2 b b b MEA3: Temperature sensor 5 module 2 b b b MEA4: Temperature sensor 6 module 2 b b b MEA5: Temperature sensor 7 module 2 b b b MEA6: Temperature sensor 8 module 2 b b b Additional measurements information elements MEA to MEA3 MEA: Residual current I0Σ b (I0Σ b b b or I0) MEA2: Residual current I0 b (I0Σ b b b or I0) MEA3: Negative sequence / unbalance T b b b b MEA4: Phase-to-phase voltage U2 b b b b MEA5: Phase-to-phase voltage U32 b b b b MEA6: Phase-to-phase voltage U3 b b b b MEA7: Residual voltage V0 b b b b MEA8: Positive sequence voltage Vd b b b b MEA9: Negative-sequence voltage Vi b b b MEA0: Power factor Cos Phi b b b MEA: Neutral-point voltage Vnt b b MEA2: Total harmonic distortion Uthd b b MEA3: Total harmonic distortion Ithd b b 2 Additional measurements information elements MEA to MEA6 MEA: Phase current I b MEA2: Phase current I 2 b MEA3: Phase current I 3 b MEA4: Residual current I 0Σ b MEA5: Residual current I 0 b MEA6: Phase-to-phase voltage U 2 b MEA7: Phase-to-phase voltage U 32 b MEA8: Phase-to-phase voltage U 3 b MEA9: Phase-to-neutral voltage V b MEA0: Phase-to-neutral voltage V 2 b MEA: Phase-to-neutral voltage V 3 b MEA2: Residual voltage V 0 b MEA3: Positive sequence voltage V d b MEA4: Negative-sequence voltage V i b MEA5: Frequency f b MEA6: Negative sequence / unbalance T b Sepam series 80 SEPED305002EN - 0/203 9
22 IEC IEC protocol 0 Sepam data table - Control direction ASDU FUN INF COT GI Sepam semantic Sepam series 20 Sepam B2X Other series 40 Sepam series System functions Initiation of general interrogation b b b b b Time synchronization b b b b b 60 General commands Enable recloser (ON) b b b b 20 Disable recloser (OFF) Sepam reset (ON) b b b b b Switching to setting group A (ON) b b b b Switching to setting group B (ON) b b b b 20 Sepam monitoring S-LAN monitoring (re)activation (ON) b b b S-LAN monitoring inhibition (OFF) Manual disturbance-recording activation b b Motor start report start command b b Data Log start command (ON) b b Data Log stop command (OFF) Phase rotation direction 23 monitoring command (ON) b b Phase rotation direction 32 monitoring command (OFF) 2 Switchgear and network commands Closing (ON) b b b b b Trip/open (OFF) Priority group shutdown (ON) b b Cancel priority group shutdown (OFF) Enable synchro-check (ON) b b Disable synchro-check (OFF) Enable voltage check (ON) b b Disable voltage check (OFF) Close capacitor step (ON) b Open capacitor step (OFF) Close capacitor step 2 (ON) b Open capacitor step 2 (OFF) Close capacitor step 3 (ON) b Open capacitor step 3 (OFF) Close capacitor step 4 (ON) b Open capacitor step 4 (OFF) Other commands Reset undercurrent protection (ON) b b b Inhibit thermal protection (ON) b b b b Confirm thermal protection (OFF) 4 Logipam group (Sepam series 80 option) TC available for the user TC6 b TC7 b to 7 20 TC0 to TC7 b 42 Logipam group 2 (Sepam series 80 option) TC available for the user to TC2 to TC29 b 43 Logipam group 3 (Sepam series 80 option) TC available for the user to TC49 to TC64 b Sepam series SEPED305002EN - 0/203
23 IEC Configuring the interfaces 0 Presentation The Sepam interfaces must be configured using SFT284 software. The IEC protocol is available with the ACE969TP-2 or ACE969FO-2 interfaces. Several parameter categories have to be configured once the interface has been selected: b The configuration parameters for the physical layer of the E-LAN port b The configuration parameters for the physical layer of the S-LAN port b The configuration parameters for functions specific to the IEC protocol (advanced S-LAN port parameters) PE8002 Access to configuration parameters These parameters can be accessed from the Communication configuration window in the SFT284 software. To access this window: b Display the Sepam configuration screen in SFT284. This screen will vary according to the type of Sepam used. b Select the Communication option. b Click : the Communication configuration window appears. b Select the type of interface used (ACE969TP-2 or ACE969FO-2). b Select the IEC03 protocol (S-LAN port). SFT284: Sepam series 80 hardware configuration. PE8003 Configuration of the E-LAN port Configuration of the physical layer The E-LAN port on the ACE969TP-2 and ACE969FO-2 interfaces is a 2-wire RS 485 port. The configuration parameters for the physical layer of the E-LAN port are: b Sepam address b Transmission speed b Parity check type Parameters Authorized values Default value Sepam address to 247 Speed 4800, 9600, 9200 or bps bps Parity No parity, Even or Odd Odd Configuration of the physical layer of the E-LAN port on an ACE969TP. Configuration tips b The Sepam address MUST be assigned before Sepam is connected to the E-LAN network. b You are also strongly advised to set the other physical layer configuration parameters before connecting to the network. b Modifying the configuration parameters during normal operation will not disturb Sepam but will reset the E-LAN port. If SFT284 is connected to Sepam via the E-LAN network, any between Sepam and SFT284 will be interrupted. SEPED305002EN - 0/203 2
24 IEC Configuring the interfaces 0 PE8003 Configuration of the S-LAN port: Physical layer The configuration parameters will vary depending on the interface selected: ACE969TP or ACE969FO. ACE969TP: 2-wire RS 485 S-LAN port The configuration parameters for the physical layer of the S-LAN port on the ACE969TP are: b Sepam address b Transmission speed b Parity check type Parameters Authorized values Default value Sepam address 0 to 254 Speed 4800, 9600, 9200 or 9200 bps bps Parity No parity, Even or Odd Even Configuration of the physical layer of the S-LAN port on an ACE969TP. PE8004 ACE969FO: Fiber-optic S-LAN port The configuration parameters for the physical layer of the S-LAN port on the ACE969FO-2 are: b Sepam address b Transmission speed b Parity check type b Link idle state: Light On or Light Off b Echo mode: Yes or No Echo mode must be activated when the Sepam is connected to an optical ring network. Parameters Authorized values Default value Sepam address 0 to 254 Speed 4800, 9600, 9200 or 9200 bps bps Parity No parity, Even or Odd Even Link idle state Light Off or Light Off Light On Echo mode Yes (optical ring) or No (optical star) No Configuration of the physical layer of the S-LAN port on an ACE969FO. Configuration tips b The Sepam address MUST be assigned before Sepam is connected to the S-LAN network. b You are also strongly advised to set the other physical layer configuration parameters before connecting to the network. b Modifying the configuration parameters during normal operation will not disturb Sepam but will reset the S-LAN port. 22 SEPED305002EN - 0/203
25 IEC Configuring the interfaces 0 Configuration of the S-LAN port: IEC protocol Configuration of the IEC protocol functions The configuration of the IEC protocol functions is identical whether the ACE969TP-2 interface or the ACE969FO-2 interface is used. Click the Advanced parameters button in the ACE969-2 configuration windows to open the IEC 03 Protocol parameters window, in which the following can be configured: b The standard parameters as defined by standard IEC b The Sepam private data to be exchanged with the supervisor PE8005 Configuration of the standard parameters The standard IEC protocol parameters are as follows: b Cyclic ASDU period b Inactivity timer b Time synchronization period b Blocking of monitoring direction Configuration of the IEC protocol. Cyclic ASDU period Period during which cyclic data, such as measurement information, is generated and updated by Sepam. This parameter, which is expressed in seconds, must be set consistently with the interval at which this data is polled by the supervisor. Inactivity timer In normal operation, the supervisor sends polling requests to the Sepam units at regular intervals. Each Sepam monitors the activity of the supervisor by checking that polling requests are being received regularly. If a Sepam fails to receive requests during a configurable period (the inactivity time delay), it will lock its port and cease to respond to requests sent subsequently by the supervisor. To re-establish with a locked Sepam, the supervisor must initiate a reset. Time synchronization period Time synchronization is transmitted via ASDU 6. If this ASDU has not been received at the end of time T (time synchronization period), Sepam will assume that its clock setting may be inaccurate and will assign the information "Invalid time" to time-tagged data. Blocking of monitoring direction Sepam can suspend the transmission of data in the monitoring direction, in accordance with the procedure specified by IEC Parameters Authorized values Default value Cyclic ASDU period 0 to 60 seconds 0 seconds Inactivity timer 0 to seconds 0 (infinite) Time synchronization period 0 to minutes 0 Blocking of monitoring direction No or Yes No SEPED305002EN - 0/203 23
26 IEC Configuring the interfaces 0 Selection of the data to be exchanged Sepam private data is categorized in three subsets: b States and indications b Protections b Measurements In each subset, the data is organized into functional groups. A functional group is identified by a function number (FUN). The data groups to be exchanged with the supervisor can be selected in the configuration window. Only the data groups required for the application should be selected, in order to avoid overloading unnecessarily (in particular in the event of a general interrogation on the part of the supervisor). PE8005 FUN Function Sepam series 20 Sepam Sepam Sepam B2X Other series 40 series 60 series 80 States and indications 20 Sepam supervision b b b b b 2 Switchgear and network NA b b b b 22 Logic equations NA NA v v v 3 Logic inputs (MES no. ) v v v v v 32 Logic inputs (MES no. 2) NA NA NA v v 33 Logic inputs (MES no. 3) NA NA NA NA v 4 Logipam (group ) NA NA NA NA v 42 Logipam (group 2) NA NA NA NA v 43 Logipam (group 3) NA NA NA NA v Protections 00 Overcurrent protections NA b b b b 0 Directional NA NA b b b current protections 02 Voltage protections b NA b b b 03 Frequency protections b NA b b b 04 Motor/generator protections NA b b b b 05 Miscellaneous protections NA b b b b Configuration of the IEC protocol. 06 Thermal protections NA b b b b 07 Power protections NA NA b b b 08 Differential protections NA NA NA b b 09 Speed protections NA NA NA b b Measurements 0 Temperature measurements NA v v v v Additional measurements b b b b b 2 Additional measurements 2 NA NA NA NA v b Function available and selected by default v Function available and not selected by default NA (Not Applicable): Function not available for a Sepam series, not displayed in the IEC03 Protocol parameters window 24 SEPED305002EN - 0/203
27 IEC Commissioning and diagnosis 0 DANGER HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS b Only qualified personnel should install this equipment. Such work should be performed only after reading this entire set of instructions and checking the technical characteristics of the device. b NEVER work alone. b Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of backfeeding. b Always use a properly rated voltage sensing device to confirm that all power is off. b Start by connecting the device to the protective earth and to the functional earth. b Screw tight all terminals, even those not in use. Failure to follow these instructions will result in death or serious injury. Installation and operating instructions for Sepam The interfaces must be installed and connected in accordance with the instructions in each Sepam user s and operation manual. b Sepam series 20 user s manual, reference PCRED30005EN, b Sepam series 40 user s manual, reference PCRED30006EN, b Sepam series 60 user s manual, reference PCRED3007EN, b Sepam series 80 operation manual, reference SEPED303003EN. Preliminary checks The following preliminary checks must be made: b Check the CCA62 cord connection between the ACE969-2 interface and the Sepam base unit. b Check the auxiliary power supply connection to the ACE b Check the connection between the S-LAN port and the ACE b Check the complete configuration of the ACE Checking the operation of the ACE969-2 interface You can use the following to check that the ACE969-2 interface is operating correctly: b The indicator LEDs on the front panel of the ACE969-2 b The information provided by the SFT284 software connected to Sepam: v On the Diagnosis screen v On the Communication configuration screens PB03454 Indicator LEDs on the ACE969-2 b Green "on" LED: ACE969-2 energized b Red "key" LED: ACE969-2 interface status v LED off: ACE969-2 configured and operational v LED flashing: ACE969-2 configuration error or ACE969-2 not configured v LED on: ACE969-2 error b S-LAN and E-LAN Tx / Rx LEDs: v S-LAN Tx LED flashing: Sepam transmitting v S-LAN Rx LED flashing: Sepam receiving v Tx and Rx off: RS 485 is idle v Tx or Rx LED is "on" while the RS 485 network is idle: the idle voltage state of the RS 485 network is incorrect ACE969TP-2 interface. PE8006 SFT284: Sepam series 80 diagnosis screen. Diagnosis using SFT284 software Sepam diagnosis screen When connected to Sepam, the SFT284 software informs the operator of the general Sepam status and of the Sepam status in particular. All Sepam status information appears on the Sepam diagnosis screen. Sepam diagnosis The operator is provided with the following information to assist with identifying and resolving problems: b Name of the protocol configured b IEC interface version number b Number of frames received b Number of mistaken frames received These two counters are reset to zero if: b The maximum value (65535) is reached b The Sepam auxiliary power supply is lost b The parameters are modified SEPED305002EN - 0/203 25
28 IEC Commissioning and diagnosis 0 Troubleshooting assistance The following diagnosis information indicates whether Sepam and a supervisor are communicating correctly using the IEC protocol: b Indicator LEDs on the front panel of the ACE969-2: v Green "on" LED on v Red "key" LED off v S-LAN Rx and Tx LEDs flashing b Sepam diagnosis screen: v Name of the protocol configured: IEC v IEC interface version number displayed v Number of frames received increasing at regular intervals v Number of mistaken frames received not increasing Deviations from the above indicate that between Sepam and the supervisor has failed. The table below lists the possible causes of failures, along with the associated course of action to be taken in each case. Symptoms Possible cause Action/Remedy ACE969-2 LEDs SFT284 diagnosis "On" LED off Protocol =???? and/or Version =???? "Key" LED on Protocol =???? and/or Version =???? "Key" LED flashing Protocol =???? and/or Version =???? S-LAN Rx LED flashing S-LAN Rx LED flashing S-LAN Rx LED off Tx or Rx LED is "on" while the RS 485 network is idle. Increase in mistaken frame counter value The frame counter values are not increasing. No power supply to ACE969-2 ACE969-2 failed ACE969-2 not configured ACE969-2 is not connected to Sepam. The ACE969-2 configuration is incorrect. The ACE969-2 physical layer configuration is incorrect. The protocol selected is incorrect. Check the auxiliary power supply to the ACE Replace the ACE Configure the ACE969-2 using SFT284. Check the ACE969-2 connection to Sepam. Use SFT284 to check the interface selected: ACE969TP-2 or ACE969FO-2. Use SFT284 to check the following parameters: b Transmission speed b Parity Check the protocol selected. The S-LAN network is not properly connected. Check the connection of the S-LAN network and the RS 485 remote power supply. The supervisor is not sending frames to Sepam. Use SFT284 to check the Sepam address parameter and check that the supervisor is sending frames to Sepam. The protocol selected is Check the protocol selected. incorrect. The supervisor is not sending frames on the Check that the supervisor is operating correctly. network. The S-LAN network is not properly connected. Check the connection of the S-LAN network and the RS 485 remote power supply. The idle voltage state of the RS 485 network is incorrect. b Check that the pull-up and pull-down bias resistors are correctly installed on the RS 485 network. b Check that the 2 load resistors are correctly installed at each end of the RS 485 network. 26 SEPED305002EN - 0/203
29 IEC Commissioning and diagnosis 0 Firmware version Firmware version release date Improvements Firmware modifications The table below describes the firmware version history of the ACE969. The following information is provided for each firmware version: b release date b improvements, b new features added. New features V.0 July 2005 First commercial version V Addition of new information, in particular: 2FL and 46BC functions and SLAN monitoring. V Transfer of the new records: Motor Start Report, Motor Trend, Data log. Activation of new recordings by commands and associated status information. Transfer of the Out-of-sync context record. Updated protocol firmware components. Correction of the anomalies below may have an impact on types of use not compliant with the protocol: b ACE969 process a second command while the first command was still executing. b Since the inactivity time delay is inoperative, the port does not lock. SEPED305002EN - 0/203 27
30 IEC Appendix : Sepam data coding 0 Presentation The Monitoring and Control data managed by Sepam is coded in accordance with the structure of standard ASDUs as specified in standard IEC ASDU COT Monitoring Control Description direction direction b Changes of state 9 b States in response to general interrogation 2 b Protection equipment tripping indication 5 3,4,5 b Identification 9 2 b Measurements b Commands Status information coding: ASDU and ASDU 2 Information on Sepam states and indications is coded using ASDU and ASDU 2. It is obtained via requests to scan class data. ASDU Bytes Description ASDU number 2 8h Structure qualifier 3 or 9 COT: (spontaneous) or 9 (General Interrog. resp.) ASDU common address: Sepam address 5 FUN FUN: function number 6 INF INF: information number 7 DPI DPI (Double Point Information): =OFF - 2=ON 8 Milliseconds (least significant byte) 9 Time-tagged Milliseconds (most significant byte) label 0 Minutes + invalidity bit (most significant bit) Hours + Summer time bit (most significant bit) 2 Additional information: 0 if COT= General interrogation number if COT=9 ASDU 2 Bytes Description 2 ASDU number 2 8h Structure qualifier 3 COT: (spontaneous) ASDU common address: Sepam address 5 FUN FUN: function number 6 INF INF: information number 7 DPI DPI (Double Point Information): =OFF - 2=ON 8 0 REL: Relative time elapsed between appearance 9 0 of the fault and tripping (not managed by Sepam) 0 0 FAN: Fault number (not managed by Sepam) 2 0 Milliseconds (least significant byte) 3 Time-tagged Milliseconds (most significant byte) label 4 Minutes + invalidity bit (most significant bit) 5 Minutes + Summer time bit (most significant bit) 6 Additional information: 0 if COT= General interrogation number if COT=9 28 SEPED305002EN - 0/203
31 IEC Appendix : Sepam data coding 0 Sepam identification: ASDU 5 ASDU 5 is generated by Sepam in response to initialization commands sent by the master: b Reset CU (Communication Unit) b Reset FCB (Frame Count Bit) IEC is only operational after initialization by the master station. In response to this initialization request, Sepam generates two successive ASDU 5 type messages. ASDU 5 in response to Reset CU First ASDU 5 message: COT = 4 (Reset CU) and INF = 3 Second ASDU 5 message: COT = 5 (Start/restart) and INF = 4 ASDU 5 in response to Reset FCB First ASDU 5 message: COT = 3 (Reset FCB) and INF = 2 Second ASDU 5 message: COT = 5 (Start/restart) and INF = 4 Once has been established, if the master sends a new initialization request, only the first ASDU 5 message is generated. ASDU 5 Bytes Description 5 ASDU number 2 8h Structure qualifier 3 COT COT: 3, 4 or 5 ASDU common address: Sepam address 5 FUN FUN: function number 6 INF INF: information number 2, 3 or Compatibility level 8 "S" (level 2: Sepam does not support IEC generic services) 9 "E" 0 " " "S" Manufacturer identification (8 ASCII characters) 2 "E" "SE SEPAM" 3 "P" 4 "A" 5 "M" 6 "G" Application software identification (4 ASCII 7 "4" 8 "0" 9 " " characters) For example, "G40 " for Sepam series 40 Generator application SEPED305002EN - 0/203 29
32 IEC Appendix : Sepam data coding 0 Measurement coding: ASDU 9 Sepam measurements are coded using ASDU 9. They are obtained via requests to scan class 2 data. The size of ASDU 9 depends on the number of measurements provided. The number of measurements is shown in the Structure qualifier field. ASDU 9 Bytes Description 9 ASDU number 2 n Number of measurements coded in ASDU 3 2 COT: 2 (cyclical) ASDU common address: Sepam address 5 FUN FUN: function number 6 INF INF: information number 7 MES Measurement (least significant byte) 8 Measurement (most significant byte) MES n Measurement n (least significant byte) Zz Measurement n (most significant byte) Where Zz = x (n - ) Each measurement is coded on 2 bytes. The value provided is a value standardized by IEC which is coded as a 3-bit 2's complement value (bits 3 to 5). It is expressed in relation to a reference value. Bit 0 is the overflow bit (OV: Overflow) Bit is the error bit (ERR) Bit 2 is a reserved bit (RES); it is always 0 Most significant byte Least significant byte Signed IEC standardized value on 3 bits RES ERR OV The actual value measured by Sepam is obtained from the IEC standardized value using the following formula: Standardized value CEI + Measured value = Reference value Sepam provides different types of measurements for which the reference values are: Measurement types Reference value Dynamic Currents.2 x Rated current 20% Voltages.2 x Rated voltage 20% Powers (P, Q).2 x U x I x 3 20% Frequencies.2 x Rated frequency 20% Negative sequence/.2 20% unbalance, total harmonic distortion, etc. Cos Phi 00% Temperature 200 C 00% For example, if the rated current on Sepam is set to 630 A, the current value coded as 325 represents a measured current equal to 600 A. The value 325 (0CB3h) is coded: Most significant byte Least significant byte Signed IEC standardized value on 3 bits RES ERR OV C B SEPED305002EN - 0/203
33 IEC Appendix : Sepam data coding 0 Command coding: ASDU 20 Commands are sent to Sepam (enable/disable functions, open/close, remote controls, etc.) via ASDU 20. A command is always confirmed by Sepam through generation of an acknowledgement message by return using ASDU (COT 20). The General Command ASDU includes an identification number (Return Information Identifier, from 0 to 255), selected arbitrarily by the master. This number is copied as is by Sepam into the Command Acknowledgement ASDU so that a link can be established with the Command ASDU. The value of the command is coded in the DCI (Double Command Information) byte; the authorized values are OFF () and ON (2). ASDU 20 Bytes Description 20 ASDU number 2 8h Structure qualifier 3 20 COT: 20 (general command) ASDU common address: Sepam address 5 FUN FUN: function number 6 INF INF: information number 7 DCI DCI (Double Command Information): =OFF - 2=ON 8 RII RII: Return Information Identifier SEPED305002EN - 0/203 3
34 IEC Appendix 2: File transfer 0 General Presentation Sepam records information, in the form of files, produced by the following functions: b Disturbance records b For Sepam series 60 and Sepam series 80 only: v Tripping contexts v Out-of-sync context v Motor Start v Motor Trend v Data Log These files can be retrieved using a file transfer procedure based on private ASDUs 254 and 255. Types of file to be transferred Definitions The files that can be transferred from Sepam to the supervisor are: b DR (Disturbance Records) directory file, which contains the information required for transferring disturbance record files saved in Sepam b TR (Tripping Records) directory file, which contains the information required for transferring Tripping context files saved in Sepam b NS (Out-of-sync context) directory file, which contains the information required for transferring Out-of-sync context files saved in Sepam b MS (Motor Start) directory file, which contains the information required for transferring Motor Start files saved in Sepam b MT (Motor Trend) directory file, which contains the information required for transferring Motor Trend files saved in Sepam b DL (Data Log) directory file, which contains the information required for transferring Data Log files saved in Sepam b Disturbance record files, which contain data saved in Sepam on events via the Disturbance recording function b Tripping context files, which contain data saved by Sepam on tripping b The Out-of-sync context file, which contains data saved in Sepam when there is a lack of synchronization b Motor Start files, which contain data saved in Sepam on motor starting b Motor Trend files, which contain data saved in Sepam when this data is calculated (on motor starting) b Data Log files, which contain data saved in Sepam on tripping of this function 32 SEPED305002EN - 0/203
35 IEC Appendix 2: File transfer 0 General File names Each file is identified by a name coded in ASCII-character. File File name Size of file name (in bytes) DR directory DR 2 Disturbance records yyyy-mm-dd-hh-mn-sssss 22 TR directory TR 2 Tripping contexts yyyy-mm-dd-hh-mn-sssss 22 NS Out-of-sync context NS 2 directory Out-of-sync context yyyy-mm-dd-hh-mn-sssss 22 MS Motor Start directory MS 2 Motor Start file yyyy-mm-dd-hh-mn-sssss 22 MT Motor Trend directory MT 2 Motor Trend file yyyy-mm-dd-hh-mn-sssss 22 DL Data Log directory DL 2 Data Log file yyyy-mm-dd-hh-mn-sssss 22 The name of Disturbance record and Tripping context files is encoded with the date the file is saved by Sepam: b yyyy: year coded on 4 ASCII characters b mm: month coded on 2 ASCII characters, from 0 to 2 b dd: day coded on 2 ASCII characters, from 0 to 3 b hh: hour coded on 2 ASCII characters, from 00 to 23 b mn: minutes coded on 2 ASCII characters, from 00 to 59 b sssss: milliseconds coded on 5 ASCII characters, from to Transfer principle A Disturbance record file is transferred from Sepam to the supervisor in three stages:. The DR directory file is read by the supervisor 2. The contents of the DR file is interpreted by the supervisor, to identify the Disturbance record file to be transferred 3. The selected Disturbance record file is read The other files (Tripping context, Out-of-sync context, Motor Start, Motor Trend, and Data Log) are transferred in the same way, using the directory files TR, NS, MS, MT and DL, respectively. SEPED305002EN - 0/203 33
36 IEC Appendix 2: File transfer 0 General Reading a file Procedure The same procedure applies for reading all files (directory files and data files). This consists of an exchange of requests/responses between the supervisor and Sepam: b The supervisor sends requests based on ASDU 254 (private ASDU). b Responses from Sepam are retrieved by the supervisor via requests to scan class data. Responses from Sepam are based on ASDU 255 (private ASDU). A file is read in three stages:. The file to be transferred is opened via an Open request/response 2. Data is transferred from the file through a succession of Read Block requests/ responses 3. The file is closed via a Close request/response Notes b Only one file can be open at any one time: the directory must therefore be closed after reading, in order to be able to read one of the files in this directory. b For an open file, only one transfer is permitted at any one time. b A data block contains a maximum of 238 bytes. The number of Read Block requests necessary to transfer a file depends on its size. ASDU requests and responses ASDU FUN Control direction Monitoring direction Description b Open request b Open response b Read Block request b Read Block positive response b Read Block negative response b Close request b Close response 34 SEPED305002EN - 0/203
37 IEC Appendix 2: File transfer 0 General Checking and processing errors Sepam performs a series of checks to ensure that a file is read correctly. Any error that occurs whilst a file is being read causes the file to be closed automatically by Sepam. Block number sequence check Data blocks are numbered starting at 0. Blocks must be read in ascending order. It is possible to reread the same block i several times, as long as no request has been made for the next block i+ to be read. A sequence error in the block number requested in a Read Block request generates a negative Read Block response (status = incorrect block number). Data integrity check A Disturbance record file, Tripping context, Out-of-sync context, Motor Start, Motor Trend or Data Log file in Sepam can be overwritten at any time by a new record if a new event occurs. If a file is in the process of being read, then data obtained by the supervisor will be corrupt. Sepam indicates this error scenario in the Read Block negative response (status = file corrupted). Once the file is corrupted, it closes automatically. In this case, the Close request serves no purpose. However the response to the Close request will be: status = incorrect file identifier. Inactivity check: aborting a read operation Sepam manages an inactivity time delay when a file read operation has been initialized, and throughout the entire course of the read operation. If there is more than 60 seconds between two Read Block requests or between the last Read Block request and the Close request, Sepam automatically closes the file. A spontaneous Close response is generated by Sepam (status = file closed on detection of inactivity). Execution reports Responses from Sepam contain an execution report coded in the Status field of ASDU 255. The values possible in the Status field are listed in the table below: Status Description 0 OK 3 Open error response: file does not exist 5 Open error response: file already open 6 Read Block negative response and Close error response: file identifier incorrect 6 Read Block negative response and Close error response: file not open 7 Spontaneous Close response: file closed on detection of inactivity 9 Read Block negative error response: file corrupted 20 Read Block negative response: block number incorrect SEPED305002EN - 0/203 35
38 IEC Appendix 2: File transfer 0 ASDU coding Presentation ASDU 254 and 255 are used to perform the 3 steps necessary for reading a file: b Open the file b Read the data blocks b Close the file Coding of the request from the supervisor (ASDU 254) and coding of the response from Sepam (ASDU 255) is given for each step. Opening a file Open request Champ Taille Description (octets) Link address 254 ASDU number 0x8 Variable Structure Qualifier 27 Cause of Transmission Common Address ASDU 05 FUN function number X Request number, selected arbitrarily by the supervisor n Length of the file name to be opened Octet... Octet n n Name of the file to be opened Open response Champ Taille Description (octets) Link address 255 ASDU number 0x8 Variable Structure Qualifier 27 Cause of Transmission Common Address ASDU 05 FUN function number X Number of the corresponding Open req. Status Execution report Least significant 4 File identifier This identifier must be used in Read Block and Close requests Most significant Least significant 4 File size in bytes (value on 32 bits) Most significant 36 SEPED305002EN - 0/203
39 IEC Appendix 2: File transfer 0 ASDU coding Reading a data block Read Block request Field Taille Description (octets) Link address 254 ASDU number 0x8 Variable Structure Qualifier 27 Cause of Transmission Common Address ASDU 0 FUN function number 4 Open file identifier (provided by Sepam in the Open response) 4 Block number to be read Read Block positive response Field Size Description (bytes) Link address 255 ASDU number 0x8 Variable Structure Qualifier 27 Cause of Transmission Common Address ASDU 0 FUN function number 4 Open file identifier 4 Block number read (most significant bit at if last block) n Block size in bytes Octet... Octet n n Block data For the last block, the most significant bit in the Block number field is set to by Sepam. Read Block negative response Field Size Description (bytes) Link address 255 ASDU number 0x8 Variable Structure Qualifier 27 Cause of Transmission Common Address ASDU 03 FUN function number 4 Open file identifier Status Error report SEPED305002EN - 0/203 37
40 EC Appendix 2: File transfer 0 ASDU coding Fermeture de fichier Close request Champ Size Description (bytes) Link address 254 ASDU number 0x8 Variable Structure Qualifier 27 Cause of Transmission Common Address ASDU 06 FUN function number X Request number, selected arbitrarily by the supervisor 4 Open file identifier (provided by Sepam in the Open response) Close response Champ Size Description (bytes) Adresse Liaison 255 ASDU number 0x8 Variable Structure Qualifier 27 Cause of Transmission Common Address ASDU 06 FUN function number X Number of the corresponding Close req. 4 Open file identifier (provided by Sepam in the Open response) Status Execution report
41 IEC Appendix 2: File transfer 0 Frame sequences exchanged in order to read a file DE80245 Example : Complete read operation with no errors Control system Application layer IEC03 link layer Protection equipment IEC03 link layer Application layer Start reading: Open file Open request SEND ASDU 254 FUN 05 CONFIRM Scan class data REQUEST CLASS RESPOND ASDU 255 FUN 05 Open response Read first block Read Block (0) req. SEND ASDU 254 FUN 0 CONFIRM Scan class data REQUEST CLASS RESPOND ASDU 255 FUN 0 Read Block response Read block Read Block () req. SEND ASDU 254 FUN 0 CONFIRM Scan class data REQUEST CLASS RESPOND ASDU 255 FUN 0 Read Block () response Read last block Read Block (n) req. SEND ASDU 254 FUN 0 Scan class data Close file Close request Scan class data End of file reading REQUEST CLASS SEND ASDU 254 FUN 06 REQUEST CLASS CONFIRM RESPOND ASDU 255 FUN 0 CONFIRM RESPOND ASDU 255 FUN 05 Read Block (n) response (last block) Close response SEPED305002EN - 0/203 39
42 IEC Appendix 2: File transfer 0 Frame sequences exchanged in order to read a file DE80246 Example 2: Read operation interrupted on error (Read Block negative response) Control system Application layer IEC03 link layer Protection equipment IEC03 link layer Application layer Start reading: Open file Open request SEND ASDU 254 FUN 05 CONFIRM Scan class data REQUEST CLASS RESPOND ASDU 255 FUN Open response Read block Read Block (i) req. SEND ASDU 254 FUN 0 CONFIRM Scan class data Termination of reading on error REQUEST CLASS RESPOND ASDU 255 FUN 03 Read Block (i) negative response If an error occurs on a Read Block request, Sepam returns a negative Read Block response. The open file is automatically closed by Sepam. Example 3: Read operation interrupted on Sepam abort (spontaneous Close response) DE80247 Control system Application layer IEC03 link layer Protection equipment IEC03 link layer Application layer Read block Read Block (i) req. SEND ASDU 254 FUN Delay > 60 seconds Read block Read Block (i+) req. SEND ASDU 254 FUN 0 CONFIRM Scan class data REQUEST CLASS Termination of reading on abort RESPOND ASDU 255 FUN 03 Spontaneaous Close response If more than 60 seconds elapses between two Read Block requests or between the last Read Block request and the Close request, Sepam automatically closes the file. A spontaneous Close response is generated by Sepam (status = file closed on detection of inactivity). 40 SEPED305002EN - 0/203
43 IEC Appendix 2: File transfer 0 Use of files by the supervisor DE Directory file Read block Read File Block (i) descriptor req. SEND ASDU 254 FUN 0 DR, TR, DL, MS, MT or NS directory files A directory file is a list of file descriptors Delay > 60 seconds File 2 descriptor... File x descriptor Read block Read Block (i+) req.... Scan class data File x descriptor Termination of reading on abort... File n descriptor SEND ASDU 254 FUN 0 REQUEST CLASS Least significant CONFIRMost significant Least significant RESPOND Most significant Spontaneaous ASDU 255 Close FUN 03 6H (22) response XXh (byte )... XXh (byte 22) Size (bytes) Description File type: = Single file File size in bytes (32-bit value) Length of file name File name (22 ASCII characters) yyyy-mm-dd-hh-mn-sssss Disturbance record file DR\yyyy-mm-dd-hh-mn-sssss Disturbance records produced by Sepam are coded in COMTRADE format. This format is also the one used in the IEC standard (only the file reading procedure is different from the one defined by IEC ). A COMTRADE disturbance record consists of two standard files: b A.CFG file, which includes the record configuration parameters (definition of analog and digital channels recorded, definition of sampling characteristics) b A.DAT file, which includes the sampled values recorded for each channel The disturbance record files are stored in Sepam in the directory DR. The name of each file gives the date and time of its production. It is coded yyyy-mm-dd-hh-mn-sssss A disturbance record file produced by Sepam is structured in such a way that the COMTRADE.CFG and.dat files can be easily obtained. Structure of a Sepam disturbance record file Size Description (bytes) Low byte 2 Size in bytes (n) of the.cfg configuration data zone High byte (6-bit value).cfg zone n Configuration parameters (.CFG file, ASCII format).dat zone X Samples values (.DAT file, binary format) SEPED305002EN - 0/203 4
44 IEC Appendix 2: File transfer 0 Use of files by the supervisor Tripping context files TR\yyyy-mm-dd-hh-mn-sssss The tripping context files are stored in Sepam in the directory TR. The name of each file gives the date and time of its production. It is coded yyyy-mm-dd-hh-mn-sssss A tripping context file contains a set of measurements recorded by Sepam when a protection function trips. It consists of two parts: b Date of the context, coded on 8 bytes b List of measurements, with each measurement coded on 32 bits (4 bytes) Structure of a Sepam tripping context file Size Description (bytes) Date 8 Context date Measurement 4 List of 44 measurements Each measurement is a 32-bit numeric value coded Measurement 44 4 Measurement 45 4 on 4 bytes, from the most significant to the least significant. The tripping context date is coded on 8 bytes Reserved Reserved value, always 0 2 Year Year from 0 to Month Month from to Day Day from to Hours Hours from 0 to Minutes Minutes from 0 to 59 7 Milliseconds (most significant) Milliseconds from 0 to Milliseconds (least significant) 42 SEPED305002EN - 0/203
45 IEC Appendix 2: File transfer 0 Use of files by the supervisor The tripping context comprises the 45 measurements listed in the table below. No. Information Format Unit Tripping current phase Itrip 32NS 0. A 2 Tripping current phase 2 Itrip2 32NS 0. A 3 Tripping current phase 3 Itrip3 32NS 0. A 4 Residual current I0Σ 32NS 0. A 5 Residual current I0 32NS 0. A 6 Negative-sequence current Ii 32NS 0. A 7 Phase-to-phase voltage U2 32NS V 8 Phase-to-phase voltage U32 32NS V 9 Phase-to-phase voltage U3 32NS V 0 Phase-to-neutral voltage V 32NS V Phase-to-neutral voltage V2 32NS V 2 Phase-to-neutral voltage V3 32NS V 3 Residual voltage V0 32NS V 4 Positive sequence voltage Vd 32NS V 5 Negative-sequence voltage Vi 32NS V 6 Frequency f 32NS 0.0 Hz 7 Active power P 32S kw 8 Reactive power Q 32S kvar 9 Apparent power S 32S kva 20 Additional tripping current I trip 32NS 0. A 2 Additional tripping current I trip2 32NS 0. A 22 Additional tripping current I trip3 32NS 0. A 23 Additional residual current I 0Σ 32NS 0. A 24 Additional residual current I 0 32NS 0. A 25 Additional negative-sequence current I i 32NS 0. A 26 Phase-to-phase voltage U 2 32NS V 27 Phase-to-phase voltage U 32 32NS V 28 Phase-to-phase voltage U 3 32NS V 29 Phase-to-neutral voltage V 32NS V 30 Phase-to-neutral voltage V 2 32NS V 3 Phase-to-neutral voltage V 3 32NS V 32 Residual voltage V 0 32NS V 33 Positive sequence voltage V d 32NS V 34 Negative-sequence voltage V i 32NS V 35 Frequency f 32NS 0.0 Hz 36 Neutral-point voltage Vnt 32NS V 37 H3 neutral-point voltage V3nt 32NS 0.% 38 H3 residual voltage V3r 32NS 0.% 39 Differential current Id 32NS 0. A 40 Differential current Id2 32NS 0. A 4 Differential current Id3 32NS 0. A 42 Through current It 32NS 0. A 43 Through current It2 32NS 0. A 44 Through current It3 32NS 0. A 45 Phase rotation mode 32NS 0=23/=32 The tripping context measurements are 32-bit numeric values coded on 4 bytes, from the most significant to the least significant. The following formats are used: b 32 NS: 32-bit non-signed value b 32 S: 32-bit signed 2's complement value SEPED305002EN - 0/203 43
46 IEC Appendix 2: File transfer 0 Use of files by the supervisor Data Log files DL\yyyy-mm-dd-hh-mn-sssss Data Log records produced by Sepam are coded in COMTRADE format. This format is also the one used in the IEC standard (only the file reading procedure is different from the one defined by IEC ). A COMTRADE Data Log record consists of two standard files: b A.CFG file, which includes the record configuration parameters (definition of analog and digital channels recorded, definition of sampling characteristics) b A.DAT file, which includes the sampled values recorded for each channel The Data Log record files are stored in Sepam in the directory DL. The name of each file gives the date and time of its production. It is coded yyyy-mm-dd-hh-mn-sssss A Data Log record file produced by Sepam is structured in such a way that the COMTRADE.CFG and.dat files can be easily obtained. Structure of a Sepam Data Log record file Size Description (bytes) Low byte 2 Size in bytes (n) of the.cfg configuration data zone High byte (6-bit value).cfg zone n Configuration parameters (.CFG file, ASCII format).dat zone X Samples values (.DAT file, binary format) Motor Start file MS\yyyy-mm-dd-hh-mn-sssss Motor Start records produced by Sepam are coded in COMTRADE format. This format is also the one used in the IEC standard (only the file reading procedure is different from the one defined by IEC ). A COMTRADE Motor Start record consists of two standard files: b A.CFG file, which includes the record configuration parameters (definition of analog and digital channels recorded, definition of sampling characteristics) b A.DAT file, which includes the sampled values recorded for each channel The Motor Start record files are stored in Sepam in the directory MS. The name of each file gives the date and time of its production. It is coded yyyy-mm-dd-hh-mn-sssss A Motor Start record file produced by Sepam is structured in such a way that the COMTRADE.CFG and.dat files can be easily obtained. Structure of a Sepam Motor Start record file Size Description (bytes) Low byte 2 Size in bytes (n) of the.cfg configuration data zone High byte (6-bit value).cfg zone n Configuration parameters (.CFG file, ASCII format).dat zone X Samples values (.DAT file, binary format) 44 SEPED305002EN - 0/203
47 IEC Appendix 2: File transfer 0 Use of files by the supervisor Motor Trend file MT\yyyy-mm-dd-hh-mn-sssss Motor Trend records produced by Sepam are coded in COMTRADE format. This format is also the one used in the IEC standard (only the file reading procedure is different from the one defined by IEC ). A COMTRADE Motor Trend record consists of two standard files: b A.CFG file, which includes the record configuration parameters (definition of analog and digital channels recorded, definition of sampling characteristics) b A.DAT file, which includes the sampled values recorded for each channel The Motor Trend record files are stored in Sepam in the directory MT. The name of each file gives the date and time of its production. It is coded yyyy-mm-dd-hh-mn-sssss A Motor Trend record file produced by Sepam is structured in such a way that the COMTRADE.CFG and.dat files can be easily obtained. Structure of a Sepam Motor Trend record file Size Description (bytes) Low byte 2 Size in bytes (n) of the.cfg configuration data zone High byte (6-bit value).cfg zone n Configuration parameters (.CFG file, ASCII format).dat zone X Samples values (.DAT file, binary format) Out-of-Sync Context files NS\yyyy-mm-dd-hh-mn-sssss The Out-of-sync context file is stored in Sepam in the directory NS. The file name gives the date and time of its production. It is coded yyyy-mm-dd-hh-mn-sssss An Out-of-sync context file contains a set of measurements recorded by Sepam during a synchronisation attempt. It consists of two parts: b Date of the context, coded on 8 bytes b List of measurements Structure of a Sepam out-of-sync context file Size Description (bytes) Date 8 Context date Measurement 4 List of the 3 measurements Measurement 2 2 Measurement 3 2 The Out-of-sync context comprises the 3 measurements listed in the table below. No. Information Format Unit Voltage difference - du 32NS 0.% of Uns Sync 2 Frequency difference - df 6NS 0,00 Hz 3 Phase difference - dphi 6NS 0, SEPED305002EN - 0/203 45
48
49
50
51
52 ART Schneider Electric - All rights reserved Schneider Electric Industries SAS 35, rue Joseph Monier CS F Rueil-Malmaison Cedex RCS Nanterre Share capital SEPED305002EN/7 As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Printed on recycled paper. Production: Assystem France Publication: Schneider Electric Printed: 0/203
Why SSD failed after abnormal power-off?
Why SSD failed after abnormal power-off? Considering the SSD must be based on FTL to realize the data transfer between logical address and physical address, if there happens abnormal power-off in case
About QDenetim and QDestek (Sistem Danışmanlık)
About QDenetim and QDestek (Sistem Danışmanlık) Sistem Danışmanlık began its operations in 2001 and continues to improve its products and services to enhance its customers' performances and productivity.
ShenZhen Renice Technology Co., Ltd. PCIe M SSD. Datasheet V
ShenZhen Renice Technology Co., Ltd PCIe M.2 2280 SSD Datasheet V1.0 2018-6-15 CATALOGUE 1. INTRODUCTION... 2 1.1 PRODUCT OVERVIEW... 2 1.2 FEATURE... 2 2. FUNCTIONAL BLOCK DIAGRAM... 3 3. PRODUCT SPECIFICATIONS...
Renice NFA100 NandFlash Test Platform
Test Tray Chamber Pile up the probe board and press Layer1 Layer2 Layer3 Layer4 Layer5 Layer6 Layer7 Layer8 Layer9 Layer10 Contorol BOX Renice NFA100 NandFlash Test Platform Accurate and Fast Nand flash
Fire Resistant Fiber Optic Cable, Fire proof fiber optic cable, Central Loose Tube Double LSZH Jacket Indoor/outdoor Type
A-DQ(MK)(BN)H(SR)H Central Loose Tube Double LSZH Jacket Indoor/outdoor Type Fire Resistant Fiber Optic Cable Overview - A-DQ(MK)(BN)H(SR)H Central Loose Tube Double LSZH Jacket Indoor/outdoor Type Fire
Interfacing a GPS Receiver with a Microprocessor via UART
ECE 480 DESIGN TEAM 6 Interfacing a GPS Receiver with a Microprocessor via UART Michael Carpenter Dr. Shanker Balasubramaniam Facilitator Application Note Friday, November 13, 2009 Executive Summary For
Renice R-SATA Storage Solution for Aerospace and Defense Application
Renice R-SATA Storage Solution for Aerospace and Defense Application The Aerospace and Defense Industries: Unique Challenges Aerospace and Defense storage applications require the highest level of reliability,often
. Condensing Water Heater Daxom. Industrial Type TS 615 EN 26
Wall Hung Boilers Water Heaters Daxom Condensing Water Heater Industrial Type TS 615 EN 26 2195 Condensing Water Heater Daxom 33 lt (UKDAX -33BT) / 20 lt (UKDAX-20BT) Technical Features UKDAX-33BT Model
3 Important Pillars of a website : Sunita Network Pvt Ltd
3 Important Pillars of a website : Sunita Network Pvt Ltd There are numerous advantages of having a website and for business entities, it is must to own a website dedicated to their organization. In such
Learn how to get started with Dropbox: Take your stuff anywhere. Send large files. Keep your files safe. Work on files together. Welcome to Dropbox!
Learn how to get started with Dropbox: 1 2 3 4 Keep your files safe Take your stuff anywhere Send large files Work on files together Welcome to Dropbox! 1 Keep your files safe Dropbox lets you save photos,
Analysis of Energy Evaluation on Lighting Programs
Proceedings of the XVIII IAHS World Congress April 16-19, 2012, Istanbul, Turkey Analysis of Evaluation on Lighting Programs Res. Assist. Arzu CİLASUN Department of Architecture Yaşar University, İzmir,
Background of Wear Leveling Algorithm
1 A kind of algorithm that extend life expectancy by 3 folds : Renice Non-Balance Wear Leveling Algorithm The first portion of this article introduces the background of wear leveling and some commonly
First Solar Series 4 PV Module ADVANCED THIN FILM SOLAR TECHNOLOGY
First Solar Series 4 PV Module ADVANCED THIN FILM SOLAR TECHNOLOGY INDUSTRY BENCHMARK SOLAR MODULES As a global leader in PV energy, First Solar s advanced thin film solar modules have set the industry
Is the P/E cycle of MLC really only 3,000 times as its datasheet said?
Is the P/E cycle of MLC really only 3,000 times as its datasheet said? Firstly, let s see the conclusion that Renice draw based on the test from Nand Flash test platform NFA100. 1, the P/E cycle of some
MACHMEC. Mekanik Package Treatment Unit.
MACHMEC Mekanik Package Treatment Unit www.machinno.com.tr MACHMEC Mekanik Package Treatment Unit Using low-cost,high-capacity MACHMEC Mechanical Package Treatment Units completely manufactured from stainless
Aytok Automatic Self-Cleaning Filters
Aytok Automatic Self-Cleaning Filters Efficient filtration from 5000 down to 15 micron Aytok Automatic Self-Cleaning Filters, with their stainless steel structure, large filtration and hydraulic pressure
Wall hung electric boiler DAXOM / Naviels. Electric Boiler. Comfort and Confidence Proper To Your Life
Naviels DAXOM / Naviels Electric Boiler Comfort and Confidence Proper To Your Life Electric Boiler Daxom 10,5 ~72 kw Electric Boiler Model UKDAX-12EDT UKDAX-16EDT UKDAX-18EDT UKDAX-20EDT UKDAX-24EDT UKDAX-30EDT
BC546/547/548/549/550
Switching and Applications High oltage: BC546, CEO =65 Low Noise: BC549, BC550 Complement to BC556... BC560 NPN Epitaxial Silicon Transistor TO-92. Collector 2. Base 3. Emitter Absolute Maximum Ratings
MACHMBR. Treatme nt Units for Sewage Water.
MACHMBR Treatme nt Units for Sewage Water www.machinno.com.tr MACHMBR Treatment Units for Sewage Water MACHMBR System is and biological treatment system that combines activated sludge process and submerged
Erasmus+ KA2 (Sample Projects)
Erasmus plus projects are a kind of innovation tool that are used not in the school education system but also in other civil society structures.i have been working as a teacher and project writer for more
Daxom Plus / Daxom Hermetic Gas Water Heater
Wall Hung Boilers Water Heaters Daxom Plus / Daxom Hermetic Gas Water Heater Copper Heat Exchanger TS 615 EN 26 Hermetic Gas Water Heater Daxom Plus 12 lt (UKDAX-12CT) The Thinest Hermetic Gas Water Heater
Remotus. Robust radio remote control for safety critical industrial applications ROBUST SWEDISH DESIGN SINCE 1918
Remotus Robust radio remote control for safety critical industrial applications ROBUST SWEDISH DESIGN SINCE 1918 Content INTRODUCTION... 4 REMOTUS JUPITER... 6 TRANSMITTERS RECEIVERS REMOTUS MERCURY...
shown as follows: Fig. 2 Timing mode selection Fig. 4 Interrupt 1 Fig. 3 Interrupt 0
Design and Implementation of a Microcontroller Based LCD Screen Digital Stop Watch Mr. Khalid I. Saad, Ms. Nusrat Afrin and Mr. Rajib Mikail Abstract The stop watch is used to measure the time required
Electric Boiler Daxom. Confort and Confidence Proper To Your Life
Wall Hung Boilers Daxom Electric Boiler Confort and Confidence Proper To Your Life Electric Boiler Daxom 10,5 ~48 kw Electric Boiler Tecnical Specifications Power Dimensions (kw) L*W*H (mm) Model UKDAX-12EDT
SUN Filters,Kendi kendini temizleyen filtre,Otomatik geri yıkamalı filtre,Otomatik ters yıkamalı kum filtresi,
AUTOMATIC SELF CLEANING SYSTEM VGA1 SUN Filters 25.82 SUNFILTER VGA1 Filters are motorized compact designed models which are perfectly suitable for use in a wide range of application areas with low liquid
SERVICE MANUAL. SC-T7000 series SC-T5000 series SC-T3000 series. Confidential. Large Format Color Inkjet Printer SEIJ12008
SERVICE MANUAL Large Format Color Inkjet Printer SC-T7000 series SC-T5000 series SC-T3000 series SEIJ12008 Notice: All rights reserved. No part of this manual may be reproduced, stored in a retrieval system,
CNC MACH breakout board user manual V8 type
CNC MACH breakout board user manual V8 type 1 Catalogue CNC Router breakout board V8 type user manual... Hata! Yer işareti tanımlanmamış. 1) Brief introduction:...3 2) Breakout board drawing:...4 3) Wiring:...5
How to read the reliability of each MLC Nand chip from Page performance?
www.renice-tech.com How to read the reliability of each MLC Nand chip from Page performance? If all Page performance is basically the same when programming every time, this Nand Flash chip should be the
POWERSTRIPS WHERE DOES IT HURT? ANCIENT WISDOM MEETS NEW TECHNOLOGY
POWERSTRIPS WHERE DOES IT HURT? Is your busy life and uncomfortable mattresses causing you to move a little slower these days? If you suffer from minor aches and pains, you're not alone. Frequent pain
COIL SLITTING LINES COMBINATION OF CUT TO LENGTH & SLITTING LINE CUT TO LENGTH LINES
COIL SLITTING LINES COMBINATION OF CUT TO LENGTH & SLITTING LINE CUT TO LENGTH LINES COMPANY SACFORM Established in 2006 TEAM Engineers, technicians 35 employees SERVICE & SALES 7/24 Authorized Technical
ERP 1100 Functional Emergency Stretcher
erpomed.com.tr ERP 1100 Functional Emergency Stretcher General Specifications Full length X-ray translucent mattress platform Possibility of X-ray examination on the stretcher by C-Arm machine on stretcher
EFFECTS OF FERTILIZATION DIFFERENT LEVELS OF WATER SALINITY ON TOMATO PLANT GROWN
1997-ISHS Symposium on greenhouse management for better yield and quality in mild winters climates, Antalya, 491, 277-281 EFFECTS OF FERTILIZATION DIFFERENT LEVELS OF WATER SALINITY ON TOMATO PLANT GROWN
BL compact Fieldbus Station for CANopen 4 Analog Pt and Ni Sensor Inputs BLCCO-4M12LT-2AI-PT-2AI-PT
On-Machine kompakt fieldbus I/O blokları CANopen slave 10, 20, 50, 125, 250, 500, 800, or 1000 kbps Two 5-pin M12 male receptacles for fieldbus connection 2 rotary coding switches for node-address IP 69K
2 Power indikatör 3 Adres anahtarı 4 Data format/baud rate anahtarı 5 Digit display. 6 Modül adı. 9 DIN ray konnektörü
Uyarı TÜRKÇE Bu bilgi dökümanı sadece ürünün tanıtımı, elektrik özellikleri, kurulumu ve bağlantısını içerir. Bağlantı yapmadan önce enerjiyi kesiniz. Enerji varken herhangi bir terminale dokunmayınız.
Arýza Giderme. Troubleshooting
Arýza Giderme Sorun Olasý Nedenler Giriþ Gerilimi düþük hata mesajý Þebeke giriþ gerilimi alt seviyenin altýnda geliyor Þebeke giriþ gerilimi tehlikeli derecede Yüksek geliyor Regülatör kontrol kartý hatasý
A Plan for Center City, Philadelphia. Daniel Schack, AICP, PTP
Congestion Management Solutions for Dense Urban Corridors: A Plan for Center City, Philadelphia Presented by: Daniel Schack, AICP, PTP ITE 2010 Annual Meeting and Exhibit August 11, 2010 1 Project Background
Renice Embedded Memory & Storage Solutions in Railway Application
Renice Embedded Memory & Storage Solutions in Railway Application Control Center CF card in PIS/Control server Ticketing & Passenger Information Platform Read/Write: 100MB/70 MB/S Fully compliant with
Compact IP20 multiprotocol Ethernet I/O module 16 universal digital channels FEN20-16DXP
EtherNet/IP slave Modbus TCP slave PROFINET slave 2 RJ45 ports for the Ethernet connection Integrated Ethernet switch 10/100 Mbps, DI / DO 24 VDC, PNP Output current: 1.0 A Protection class IP20 Tip kodu
Published by: PIONEER RESEARCH & DEVELOPMENT GROUP (www.prdg.org) 33
Control of Dc Motor Based On Linear Quadratic Regulator Method Ishak ERTUGRUL, Osman ULKIR 2, Nihat AKKUS 3,2,3 Department of Mechatronics Engineering, Marmara University, Istanbul, 34722, Turkey Abstract
Get started with Google Drive
Get started with Google Drive 1 Store any file Use Drive s 15GB of free Google storage to keep anything you want. Learn how to add a file Share files and folders Everyone can see and edit files at the
BL compact Fieldbus Station for PROFIBUS-DP 8 Configurable Digital Channels BLCDP-4M12MT-8XSG-PD
On-Machine kompakt fieldbus I/O blokları PROFIBUS-DP slave 9.6 kbps 12 Mbps Two 5-pin, reverse-keyed M12 male receptacles for fieldbus connection 2 rotary coding switches for node-address IP 69K M12 I/O
Wolf Safety Lamp Company. ATEX Explained. Ex Equipment
Wolf Safety Lamp Company ATEX Explained Ex Equipment This guide is provided to aid in the selection of Wolf lighting products for use in potentially explosive atmospheres. Information given is based on
Compact IP20 multiprotocol Ethernet I/O module 4 digital inputs, 4 universal digital channels FEN20-4DIP-4DXP
FLC/ARGEE programlanabilir EtherNet/IP slave Modbus TCP slave PROFINET slave 2 RJ45 ports for the Ethernet connection Integrated Ethernet switch 10/100 Mbps 4 digital inputs 4 universal digital channels,
Teknoloji Servisleri; (Technology Services)
Antalya International University Teknoloji Servisleri; (Technology Services) Microsoft Ofis Yazılımları (Microsoft Office Software), How to Update Office 365 User Details How to forward email in Office
The Role of Social Marketing in Creating Obesity Awareness and Its Effects on Life Quality
Special Issue, International Conference on Military and Security Studies,ICMSS-2015 Research Article The Role of Social Marketing in Creating Obesity Awareness and Its Effects on Life Quality Mustafa Karadeniz
UMD-B12 UMD-B10 RF MODEM BOARD
/UMD-B10 UMD-B10 RF MODEM BOARD ÜRÜN KILAVUZU Version 1.4 (KASIM 2005)!"#! $%%&'''()*+,-. %/ ve UMD-B10 KULLANIM KILAVUZU 1 /UMD-B10 GENEL ÖZELLKLER Özellikler : * 433-434 MHz. UHF bandında EN 300 220
CHAPTER 4 NICKEL-CADMIUM BATTERIES
CHAPTER 4 NICKEL-CADMIUM BATTERIES Nickel-cadmium alkaline batteries have gained respect as a very reliable, long life electrochemical system from their performance in (4-1) industrial starter and standby
VRE SERS ELEKTRONK TERMK RÖLELER VRE SERIES ELECTRONIC THERMAL OVERLOAD RELAY
VRE SERS ELEKTRONK TERMK RÖLELER VRE SERIES ELECTRONIC THERMAL OVERLOAD RELAY Teknik Özellikler 1.Standartlar : IEC 60947-4-1, TS EN 60947-4-1 2.Depolama Sıcaklıı : - 40 0 C +70 0 C 3.Çalıma Sıcaklıı :
Table 1 Changes in FSH in the entire sample and in FSH subgroups(毺iu/ml).
309 310 Hikmet Hassa et al./ Asian Pacific Journal of Reproduction (2013)309-311 Table 1 Changes in FSH in the entire sample and in FSH subgroups(毺iu/ml). FSH values All patients Group 1 Group 2 Group
Uyarı. ❷ Özellikler. Fonksiyonlar. Ürün Profili. Ethernet Arayüz
Uyarı TÜRKÇE Bu bilgi dökümanında sadece DVPEN01-SL elektriksek özellikleri,genel özellikler,kurulum ve kablolama hakkında açıklamalar vardır. Kablolamadan önce enerjiyi kesin. Enerjide iken herhangi bir
Evaluation of Energy Performance on Lighting by Using Dialux and Bep-Tr
Evaluation of Energy Performance on Lighting by Using Dialux and Bep-Tr Res. Assist. Arzu CILASUN, Department of Architecture, Yaşar University, İzmir, Turkey [email protected] Murat ANBARCI, Istanbul
Just Enough ENGLISH GRAMMAR. Illustrated. Gabriele Stobbe
Just Enough ENGLISH GRAMMAR Illustrated Gabriele Stobbe New York Chicago San Francisco Lisbon London Madrid Mexico City Milan New Delhi San Juan Seoul Singapore Sydney Toronto Copyright 2008 by Gabriele
Information Storage and Management Version 3 Student Guide
Information Storage and Management Version 3 Student Guide Education Services August 2015 Welcome to Information Storage and Management Version 3. Copyright 2015 EMC Corporation. All Rights Reserved.
UFM-A12 WPA MODEM MODUL
UFM-A12 WPA MODEM MODUL ÜRÜN KILAVUZU Version 2.5 (TEMMUZ 2010) İVEDİK ORGANİZE SAN. BÖL. 21. CADDE 609. SOKAK NO:2 06370 OSTİM / ANKARA TEL NO :(312) 395 68 75 76 FAKS NO:(312) 395 68 77 http:// www.udea.com.tr
VIRTUAL MUSEUM and REVIEW OF VIRTUAL MUSEUMS IN TURKEY. Research Assistant Arzu Cilasun, Yasar University, Department of Architecture
VIRTUAL MUSEUM and REVIEW OF VIRTUAL MUSEUMS IN TURKEY Research Assistant Arzu Cilasun, Yasar University, Department of Architecture [email protected] Museums can be defined in many different ways.
POWERMIX PLASTER MIXING AND SPRAYING MACHINES CATALOGUE OF POWERMACHINES Construction Machines & Spare Parts
CATALOGUE OF 2017 POWERMACHINES Construction Machines & Spare Parts PRODUCT CODE: PMP0001 POWERMIX PLUS PRODUCT DESCRIPTION It is continues mixing and spraying pump machine with very high capacity which
Keyestudio SHT31 Temperature and Humidity Module / SHT31 Sıcaklık ve Nem Modülü
Keyestudio SHT31 Temperature and Humidity Module / SHT31 Sıcaklık ve Nem Modülü Overview / Genel Bakış This module mainly uses the SHT31 temperature and humidity sensor, which belongs to the SHT3X series
Security Walk Through Metal Detectors & Hand Held Metal Detectors by ThruScan - Elektral ECAC Comply manufacturer 40 years experience 20.000 sqm factory area
Yesterday, today, tomorrow.. Always with you!.. ELEKTRAL A.Ş was founded by Mr. Sayil Dincsoy (M.Sc.) in 1978 and presently continues accelerated high technology production in its 20.000 m 2 integrated
HP- SERİSİ YANGIN HİDROFOR PANOLARI FIRE FIGHTING CONTROL PANELS
HP- SERİSİ YANGIN HİDROFOR PANOLARI FIRE FIGHTING CONTROL PANELS HP SERİSİ YANGIN HİDROFOR PANOLARI Standart Özellikler 0,75 kw - 7,5 kw Direk Yolverme 7,5 kw - 560 kw Yıldız-Üçgen Yolverme NFPA Standartlarına
Estrogen deprivation can cause vaginal atrophy symptoms. Frequency and determinants of urogenital symptoms in postmenopausal Islamic women
Menopause: The Journal of The North American Menopause Society Vol. 21, No. 2, pp. 000/000 DOI: 10.1097/gme.0b013e3182937966 * 2013 by The North American Menopause Society Frequency and determinants of
PA501S/PA502S/PA502X PX702HD DLP Projektör
PA501S/PA502S/PA502X PX702HD DLP Projektör Uygunluk Bilgileri - - - - - - Kanada için - i - - ii Madde iii - - - - - ... 1 3 Projektör özellikleri... 3... 4... 5... 6 12 Bir konum seçme... 12... 13 14...
IDENTITY MANAGEMENT FOR EXTERNAL USERS
1/11 Sürüm Numarası Değişiklik Tarihi Değişikliği Yapan Erman Ulusoy Açıklama İlk Sürüm IDENTITY MANAGEMENT FOR EXTERNAL USERS You can connect EXTERNAL Identity Management System (IDM) with https://selfservice.tai.com.tr/
IMPACT OF SOCIAL MEDIA ON MARKETING:A VIEW ON SUCCESS STORIES Selçuk SERT & Utku KÖSE SOSYAL MEDYANIN PAZARLAMA ÜZERİNDEKİ ETKİSİ: BAŞARI HİKAYELERİNE BİR BAKIŞ
IMPACT OF SOCIAL MEDIA ON MARKETING: A VIEW ON SUCCESS STORIES Selçuk SERT 1 Utku KÖSE 2 Abstract As it is known, social media has a great impact on daily life because of its functions and features related
A20 KULLANIM KILAVUZU
1. Kullanım Kılavuzu 1:Montaj ve Besleme Fingerprint Access Control A20 KULLANIM KILAVUZU 2:Yönetici Şifresi doğrulama ve değiştirme. Kullanıcı parmakizi, kart ve şifre kaydı 3: Erişim ( access control)
MPC 9000 A F.01U.500.376. Ürün tanýmý / Kurulum kýlavuzu Panel kumandasý olan iþletim ve görüntü birimi
TR GB Ürün tanýmý / Kurulum kýlavuzu Panel kumandasý olan iþletim ve görüntü birimi Product description / Installation manual Operating and display unit with panel controller F.01U.500.376 HBC 0010 A CPH
24kV,630A Outdoor Switch Disconnector with Arc Quenching Chamber (ELBI) IEC IEC IEC 60129
24kV,630 Outdoor Switch Disconnector with rc Quenching Chamber (ELBI) IEC265-1 IEC 694 IEC 129 Type ELBI-HN (24kV,630,normal) Closed view Open view Type ELBI-HS (24kV,630,with fuse base) Closed view Open
A Comparison of Performance Metrics of Turkish Twitter Messages Using Text Representations
A Comparison of Performance Metrics of Turkish Twitter Messages Using Text Representations Abdullah Ammar 1*, Tolga AYDIN 1 1 1 Ataturk University, Department of Computer Engineering, Erzurum, Turkey *
Virtualmin'e Yeni Web Sitesi Host Etmek - Domain Eklemek
Yeni bir web sitesi tanımlamak, FTP ve Email ayarlarını ayarlamak için yapılması gerekenler Öncelikle Sol Menüden Create Virtual Server(Burdaki Virtual server ifadesi sizi yanıltmasın Reseller gibi düşünün
EVALUATION OF TURKEY'S FOREIGN TRADE COMPOSITION AFTER 1980 ACCORDING TO THE COUNTRIES
EVALUATION OF TURKEY'S FOREIGN TRADE COMPOSITION AFTER 1980 ACCORDING TO THE COUNTRIES ABSTRACT In this study, It was tried to analyse effects of growth rate of Turkey, EU and the World country economies,
Delta Pulse 3 Montaj ve Çalıstırma Kılavuzu. www.teknolojiekibi.com
Delta Pulse 3 Montaj ve Çalıstırma Kılavuzu http:/// Bu kılavuz, montajı eksiksiz olarak yapılmış devrenin kontrolü ve çalıştırılması içindir. İçeriğinde montajı tamamlanmış devrede çalıştırma öncesinde
AKE Bulaşık Yıkama Makinası Kontrol Kartı Kullanım Kılavuzu Dishwasher Controller User Manual TR EN
Bulaşık Yıkama Makinası Kontrol Kartı Kullanım Kılavuzu Dishwasher Controller User Manual Bulaşık Yıkama Makinası Kontrol Kartı Kullanım Kılavuzu (7 SEG SIMPLE YATAY TİP) AKE-BYM-102 Lütfen bu kullanım
Fragility analysis of mid-rise R/C frame buildings
Engineering Structures 28 (2006) 1335 1345 www.elsevier.com/locate/engstruct Fragility analysis of mid-rise R/C frame buildings Murat Serdar Kirçil,Zekeriya Polat Department of Civil Engineering, Yıldız
PCC 6505 PROFILE CUTTING LINE
PCC 6505 PROFILE CUTTING LINE 1.DESCRIPTION PCC 6505 is a servo controlled machine which is specifically designed for the serial cutting of any kind of PVC and aluminum s in the market. The machine is
Arıza Giderme. Troubleshooting
Arıza Giderme Sorun Olası Nedenler Giriş Gerilimi düşük hata mesajı Şebeke giriş gerilimi alt seviyenin altında geliyor Şebeke giriş gerilimi tehlikeli derecede Yüksek geliyor Regülatör kontrol kartı hatası
F8914 ZİGBEE RF MODEM İLE MODBUS HABERLEŞME KILAVUZU
F8914 ZİGBEE RF MODEM İLE MODBUS HABERLEŞME KILAVUZU Z Telemetri Telekomünikasyon Yazılım San. Tic. LTD. ŞTI. Kavaklıdere Mah. Atatürk Bulvarı No: 151/804 Çankaya / Ankara [email protected] Tel: +90
Fiber Optic Connectivity. Copper Connectivity. Cable. Rack Cabinet
Fiber Optic Connectivity Copper Connectivity Cable Rack Cabinet - P R O D U C T OVERVIEW 2018 Fiber Optic Connectivity Copper Connectivity Cable Rack Cabinet TABLE OF CONTENTS Fiber Optic Connectivity
Management Science Letters
Management Science Letters 7 (2017) 241 246 Contents lists available at GrowingScience Management Science Letters homepage: www.growingscience.com/msl The perspectives of banking and health sector administrators
24VDC Power girişine sahip 8 portlu 8x10/100/100Base- T(X) P.S.E Gigabit Ethernet Endüstriyel Switch
24VDC Power girişine sahip 8 portlu 8x10/100/100Base- T(X) P.S.E Gigabit Ethernet Endüstriyel Switch Özellikler 8 adet 10/100/1000Base-T(X) PoE(P.S.E) port IEEE 802.3at protokolünü destekleyerek PoE ile
aluminıum Profıle Brushıng Machine APSAM V6
aluminıum Profıle Brushıng Machine APSAM V6 Sat i naj Mak inası APSAM V6 Teknik Özellikler Fırça Hızı Makina 3 grup fırçadan oluşmaktadır.her grup alt ve üst olmak üzere iki fırçadan oluşmaktadır. senkronizasyona
"Şirket" Sunucusu ve Başarı Mobile Arasındaki HTTP Veri Aktarımı için Etkileşim Teknik Protokolü
"Şirket" Sunucusu ve Başarı Mobile Arasındaki HTTP Veri Aktarımı için Etkileşim Teknik Protokolü BAŞARI Mobile tarafından desteklenmektedir. 1. Genel Bakış Bu döküman ile Şirket Adı nın ve Basari Mobile
Varol, A., Carabott, V., Delannoy, P., Vivet, M.: Control of Temperature with a Robot, Matik'97, Makine Tasarım Teorisi ve Modern İmalat Yöntemleri
235 2.4. CONTROL OF TEMPERATURE WITH A ROBOT ABSTRACT This article is a result of a project which completed at Med- Campus, International Summer School on Computer-Based Cognitive Tools for Teaching and
Fieldbus I/O module PROFIBUS-DP 16 digital PNP outputs 2A TBDP-L2-16DOP
2 M12, 5-pin, B-coded, PROFIBUS-DP- Fieldbus connection Kuvvetlendirilmiş cam elyaf gövde Darbeye ve titreşime karşı test edilmiştir Tamamen yerleşik modül elektronikleri Koruma sınıfları IP65, IP67, IP69K
e-tartı LTR3 Firmware Upgrade Yazılım Güncelleme Moduler Connection LTR3 Firmware Upgrade / LTR3 Yazılım Güncelleme v1.0.
e-tartı LTR3 Firmware Upgrade Yazılım Güncelleme Moduler Connection www.etarti.com LTR3 Firmware Upgrade / LTR3 Yazılım Güncelleme v1.0.0 1 LTR3 Firmware Upgrade / LTR3 Yazılım Güncelleme v1.0.0 2 Contents
HİDROFOR KONTROL PANOLARI
KERİM ELEKTROMOTOR ELK. SAN. TİC. LTD. ŞTİ. HİDROFOR KONTROL PANOLARI BOOSTER PUMP kerim.com.tr MANUAL ÇALIŞMA SEÇENEĞİ Elektronik devrelerde oluşabilecek arıza durumlarında sistemin kesintiye uğramaması
About the Author. He is married with four children. He is accessible through his personal website.
About the Author Mehmet Atasever: Having begun his education life in Erzurum province, his hometown, earned a Master s Degree in Product Management and Marketing at Ataturk University. He is studying for
Energy Conversion and Management
Energy Conversion and Management 52 (2011) 615 620 Contents lists available at ScienceDirect Energy Conversion and Management journal homepage: www.elsevier.com/locate/enconman Design, construction and
Improving Energy Efficiency
BOILERS AND HEATERS Improving Energy Efficiency Natural Resources Canada Office of Energy Efficiency Ressources naturelles Canada Office de l'efficacité énergétique August 2001 Written by Paul Dockrill